5. Installation of the sub-units 

 
PolluTherm can not only be used as a heat meter 
but also as a cooling meter (optional: PolluTherm 
H, PolluTherm X H, s. a. chapter 11.10). 
Therefore the text hereinafter includes following 
terms: 
 
Return pipe of heating systems: 

Colder line

 

Supply pipe of heating systems: 

Warmer line

 

 
Return pipe of cooling systems: 

Warmer line

 

Supply pipe of cooling systems: 

Colder line

 

 

Examples of installation in heating systems: 
 

 

Figure 1: Measurement after admixing 

 

 

Figure 2: Measurement in injection system 

 

 

Figure 3: Measurement with overflow valve 

 
5.1 Flow sensor 

 
Standard installation of the flow sensor is in the 
heating return pipe i.e. the colder line. If the flow 
sensor has to be installed in the heating supply 
pipe / the warmer line, PolluTherm X has to be 
used (X means that the integrator has been 
adjusted for flow sensors in the warmer line). 
 

Installation in cooling systems: 

 
It is recommended to install the flow sensor in the 
warmer line (return pipe) of the cooling device.  
PolluTherm X (installation in warmer line) has to 
be used. Please note the approved minimum 
temperature when using Sensus flow sensors: 
 

Type AN 130 (DN20 – DN40):  

> 5 °C – 130 °C 

Type MeiStream FS (> DN50): 

> 5 °C – 90 °C 

Type Woltman

 

WPD FS (> DN 50):  > 15 °C - 130 °C  

 
An arrow on the body shows the flow direction. 
The maximum operating pressure and the 
maximum operating temperature must not be 
exceeded. When using flow sensors starting from 
nominal size DN 50 (Woltman meters). A straight 
inlet pipe (area of steady flow) has to be provided 
as follows: 
 

Type 

Area of steady flow 

WP  

Standard: 3 x DN 

WP  

After manifolds, rotary pumps, 

throttling equipment: Flow 

straightener 

and 3 x DN 

 
After the flow sensor abrupt reductions of the pipe 
cross section are not allowed. 
It is advisable to install a filter in front of the flow 
sensor or at another suitable point of the heating 
or cooling circuit as well as shut-off valves before 
and after the flow sensor (so that the pipe line 
doesn’t have to be emptied when the meter has to 
be exchanged). Install a fitting piece during the 
initial installation instead of the flow sensor and 

Содержание SENSUS PolluTherm Integrator

Страница 1: ...t into the heat meter 11 11 8 Combined heating cooling meter ordering option 11 11 9 Optional integrated data logger ordering option 12 11 10 Retrofitting from battery unit to power supply unit 12 12...

Страница 2: ...tection Only specially trained and authorized personnel are permitted to carry out the connection Moreover attention is to be paid to the national technical rules Voltage 220 240 V AC or 24 V AC Frequ...

Страница 3: ...g systems It is recommended to install the flow sensor in the warmer line return pipe of the cooling device PolluTherm X installation in warmer line has to be used Please note the approved minimum tem...

Страница 4: ...of the pipe diameter Refer to the following guide for installing such temperature sensors Nominal sizes DN 50 Install the temperature sensors in an angle of 45 towards the flow direction see figure 4...

Страница 5: ...8 Four wire connection 7 8 und 3 4 Screening if any Start by removing the appropriate preshaped rubber part from the integrator housing see figure 7 Then pull the cable through the hole in the presha...

Страница 6: ...ntervals of 4 seconds and shows the accumulated heat energy By a push on the red key the first display item in the user menu accumulated heat energy is activated The other five menus can be obtained b...

Страница 7: ...es on an adjustable annual target Target day value for heat and cooling energy resp Target day value for volume Target day value for tariff 1 if activated Target day value for tariff cold if activated...

Страница 8: ...play shows a month selectionor wait for five minutes 8 4 Service menu example Each display item is marked with a man symbol The service menu shows maximum values and meter settings Absolute maximum fl...

Страница 9: ...t three digits of the eight digit serial number on the meter housing At the beginning 000 appears Push the key for approx 2 seconds the zero on the left side starts flashing By continuously pushing th...

Страница 10: ...ow temperature sensors In most cases the error situation Err 1010 is caused by temporary system conditions where the temperature in the warmer line drops by at least 3K below the temperature in the co...

Страница 11: ...r reading 0 00 m The activation of the inputs has to be done via the service software MiniCom menu item set pulse input parameters The meter IDs of the pulse meters have to be set there as well as the...

Страница 12: ...only the screw on the right side under the KK1 seal user seal of the plastic cover Pull the integrated module forward from the connection The seals in the middle and on the left side may not be remove...

Страница 13: ...the lower 3 and 4 the electric resistance of the extension cable or cables does do not influence the measurement and the reading of the temperatures Material number 28505033 Edition 007 August 2019 Su...

Страница 14: ...Heat Cooling meter integrator PolluTherm Installation and operational instructions M H 6111 INT PolluTherm page 14 Annex 1 Declaration of conformity acc directive 2004 22EC MID...

Отзывы: