Heat / Cooling meter integrator PolluTherm 

Installation and operational instructions 

 

 
M H 6111 INT PolluTherm, page 12 

 
At an automatic switch-over point this PolluTherm 
version switches over between metering heating 
and cooling energy. The switch-over point to cool 
metering is preset in the factory to: 
 
supply flow temperature < 25 °C 

and

 

negative temperature difference > - 0,15 K 
 
Conditions to switch back to heat metering: 
 
supply flow temperature > 25 °C 

and

 

positive temperature difference > 0,15 K 
 
If required this switch-over point can be changed 
on site with the service software MiniCom, version 
3.6.0.65 or higher. 
 
 

11.9 Optional integrated data logger (ordering 
option) 

 
When the option is built in the housing lid is 
additionally labeled with „data logger“. 
 
The integrated data logger stores consumption 
values and instantaneous values (power, flow 
rate, temperatures) during a selectable time 
interval (3 to 1440 minutes). The logger data can 
be read out via the optical interface M-Bus or 
Mini-Bus with the service software MiniCom 
version 3.6.0.65 or higher. The time interval 
(factory setting: 60 minutes) can also be changed 
with MiniCom. 
 
For PC connection use either an optical data 
coupler (see chapter 11.1.) or a USB plug-in unit 
(order number: 68504688). 
 

11.10 Retrofitting from battery unit to power 

supply unit 

 
Before retrofitting please note the following 
instructions and perform in chronological order: 

 

Before you remove the supply battery from 
the integrator the integrated module has to 
be removed from the integrator. Unscrew 
only the screw on the right side under the 
KK1 seal (user seal) of the plastic cover. Pull 
the integrated module forward from the 
connection. The seals in the middle and on 
the left side may not be removed (loss of 
calibration)! 

  Insert the backup battery AA 3,6V 

(68504900) on the backside of the integrator 
module. The battery is needed for the backup 
date and for the short-term emergency use in 
case of power failure. 

 

Remove the main battery (D) and plug in the 
mains module. 

For a detailed description please refer to 
installation manual MH 1122. 
 
 

12. Information on the extension of 
temperature sensor cables 

 
The temperature sensors for PolluTherm are 
available with platinum resistor elements in: 
 
Pt 500 (500 Ohm at 0 °C) Standard 
 
For each integrator two temperature sensors are 
required. Therefore such sensors are paired 
regarding on their resistance and supplied as 
calibrated instruments. This ensures that incorrect 
temperature difference in the heating and/or 
cooling system will not be registered because of 
different characteristic curves of temperature 
sensors and cable resistance. 
 
In some systems it is often necessary to extend 
one or both temperature sensors. The length of 
the temperature sensor cables can be extended 
by max. 23 m. In order to compensate for the 
additional cable resistance so-called four-wire 
technology is applied. Use a four-wire cable (e.g. 
I-Y(St)Y 2x2x0.8, 

minimum cable size: 0.5 

mm²

). 

 
 
It is possible 
 

  to extend only one cable 

 

  to extend both cables; they do not 

necessarily need to have the same length  

 
The extension of the temperature sensors may be 
done with the junction box that is offered from 
Sensus (see figure 15, order number: 88599001, 
installation manual MH 6105). 
 

 

 

Figure 15: Connection diagram 

Содержание SENSUS PolluTherm Integrator

Страница 1: ...t into the heat meter 11 11 8 Combined heating cooling meter ordering option 11 11 9 Optional integrated data logger ordering option 12 11 10 Retrofitting from battery unit to power supply unit 12 12...

Страница 2: ...tection Only specially trained and authorized personnel are permitted to carry out the connection Moreover attention is to be paid to the national technical rules Voltage 220 240 V AC or 24 V AC Frequ...

Страница 3: ...g systems It is recommended to install the flow sensor in the warmer line return pipe of the cooling device PolluTherm X installation in warmer line has to be used Please note the approved minimum tem...

Страница 4: ...of the pipe diameter Refer to the following guide for installing such temperature sensors Nominal sizes DN 50 Install the temperature sensors in an angle of 45 towards the flow direction see figure 4...

Страница 5: ...8 Four wire connection 7 8 und 3 4 Screening if any Start by removing the appropriate preshaped rubber part from the integrator housing see figure 7 Then pull the cable through the hole in the presha...

Страница 6: ...ntervals of 4 seconds and shows the accumulated heat energy By a push on the red key the first display item in the user menu accumulated heat energy is activated The other five menus can be obtained b...

Страница 7: ...es on an adjustable annual target Target day value for heat and cooling energy resp Target day value for volume Target day value for tariff 1 if activated Target day value for tariff cold if activated...

Страница 8: ...play shows a month selectionor wait for five minutes 8 4 Service menu example Each display item is marked with a man symbol The service menu shows maximum values and meter settings Absolute maximum fl...

Страница 9: ...t three digits of the eight digit serial number on the meter housing At the beginning 000 appears Push the key for approx 2 seconds the zero on the left side starts flashing By continuously pushing th...

Страница 10: ...ow temperature sensors In most cases the error situation Err 1010 is caused by temporary system conditions where the temperature in the warmer line drops by at least 3K below the temperature in the co...

Страница 11: ...r reading 0 00 m The activation of the inputs has to be done via the service software MiniCom menu item set pulse input parameters The meter IDs of the pulse meters have to be set there as well as the...

Страница 12: ...only the screw on the right side under the KK1 seal user seal of the plastic cover Pull the integrated module forward from the connection The seals in the middle and on the left side may not be remove...

Страница 13: ...the lower 3 and 4 the electric resistance of the extension cable or cables does do not influence the measurement and the reading of the temperatures Material number 28505033 Edition 007 August 2019 Su...

Страница 14: ...Heat Cooling meter integrator PolluTherm Installation and operational instructions M H 6111 INT PolluTherm page 14 Annex 1 Declaration of conformity acc directive 2004 22EC MID...

Отзывы: