Heat / Cooling meter integrator PolluTherm 

Installation and operational instructions 

 

 
M H 6111 INT PolluTherm, page 2 

 
2. Safety instructions

 

 

 

  The installation of PolluTherm requires 

adequate professional knowledge and should 
be carried out by specially trained persons 
only.  

  Due to the danger of scalding from leaking 

heating liquid ensure proper installation when 
mounting PolluTherm, immersion sleeves or 
ball valves. Therefore close the shut-off 
valves before disassembly. 

  Depending on manufacturing conditions the 

brass connection threads might be sharp-
edged. Therefore we recommend wearing 
protection gloves.  

  Heating or cooling meters are measuring 

instruments and have to be handled with 
care. In order to protect them against 
damage and dirt they should only be taken 
from the package immediately before 
installation.  

  If the housing or the contact cables are 

damaged the device shall be taken out of 
service and secured against accidental 
reconnection. 

  Clean only with a cloth dampened in water. 

  Depending on the version the device has a 

battery. This battery may not be opened by 
force, put in contact with water, short-
circuited or exposed to temperatures of more 
than 80 °C 

  Empty batteries, electronic devices or 

components that are not needed anymore 
are special waste and have to be disposed at 
appropriate collection points. 

  To ensure fair consumption billing, when 

using several meters in one billing unit,. 
similar meter types and installation positions 
should be used. 

  Please also consider the standard EN 1434. 

 

Mains-operated devices: 

 
The power modules (230 V AC or 24 V AC) must 
be fed from supplies fused at 6 A protection. 

Only 

specially trained and authorized personnel are 
permitted to carry out the connection. 

Moreover attention is to be paid to the national 
technical rules. 
 
Voltage: 

220 ... 240 V AC 
or 24 V AC 

Frequency:  

 

50/60 

Hz 

Max. power consumption: 

0,5 VA 

Cable length:   

 

ca. 1,1 m 

 

3. Required tools 

  Appropriate spanner wrench or screw wrench 

for screw connection and flange screws 
respectively. 

  Slot screw driver 0,5 x 3 for clamp terminal 

block 

  Allen key size 3 for wall adapter 

  Side cutter for sealing wire 

  Fork wrench SW 24 (immersion sleeves) 

 

4. Combination of the sub-units 

 
Each measuring point is composed of: 
 

 Flow 

sensor 

 Integrator 

PolluTherm 

  One pair of temperature sensors (Pt 500) 

 
It must be ensured that the subdevices 
correspond to the correct connection values. For 
example, the pulse value of the calculator must 
match the pulse value of the flow sensor. Please 
note the version of the temperature sensor 
(diameter, installation length). 
 

4.1 Programming the input pulse value 

 
This paragraph is only applicable for instruments 
where no input pulse value has been pre-
programmed in the factory. 
 

Attention! 
 
Because of legal calibration regulations the 
input pulse value can only be programmed 
once. Therefore be sure that you have set the 
desired value before removing the bridge. 
Mains operated devices: make sure that the 
power supply is connected before 
programming the input pulse value. 
 

 
This variant can be programmed only once with 
one of the following input pulse values (each one 
in litres): 
 

0,25 1 

2,5  10  25 

 

100 250 1.000 

10.000 

 
For this purpose activate the display by pressing 
the red key and releasing it again. Each of the 
above mentioned programmable input pulse 
values can be selected one after the other by a 
short keystroke. Having set the required value, 
remove the bridge between terminal 1 and 2 in the 
terminal block. 
 

Содержание SENSUS PolluTherm Integrator

Страница 1: ...t into the heat meter 11 11 8 Combined heating cooling meter ordering option 11 11 9 Optional integrated data logger ordering option 12 11 10 Retrofitting from battery unit to power supply unit 12 12...

Страница 2: ...tection Only specially trained and authorized personnel are permitted to carry out the connection Moreover attention is to be paid to the national technical rules Voltage 220 240 V AC or 24 V AC Frequ...

Страница 3: ...g systems It is recommended to install the flow sensor in the warmer line return pipe of the cooling device PolluTherm X installation in warmer line has to be used Please note the approved minimum tem...

Страница 4: ...of the pipe diameter Refer to the following guide for installing such temperature sensors Nominal sizes DN 50 Install the temperature sensors in an angle of 45 towards the flow direction see figure 4...

Страница 5: ...8 Four wire connection 7 8 und 3 4 Screening if any Start by removing the appropriate preshaped rubber part from the integrator housing see figure 7 Then pull the cable through the hole in the presha...

Страница 6: ...ntervals of 4 seconds and shows the accumulated heat energy By a push on the red key the first display item in the user menu accumulated heat energy is activated The other five menus can be obtained b...

Страница 7: ...es on an adjustable annual target Target day value for heat and cooling energy resp Target day value for volume Target day value for tariff 1 if activated Target day value for tariff cold if activated...

Страница 8: ...play shows a month selectionor wait for five minutes 8 4 Service menu example Each display item is marked with a man symbol The service menu shows maximum values and meter settings Absolute maximum fl...

Страница 9: ...t three digits of the eight digit serial number on the meter housing At the beginning 000 appears Push the key for approx 2 seconds the zero on the left side starts flashing By continuously pushing th...

Страница 10: ...ow temperature sensors In most cases the error situation Err 1010 is caused by temporary system conditions where the temperature in the warmer line drops by at least 3K below the temperature in the co...

Страница 11: ...r reading 0 00 m The activation of the inputs has to be done via the service software MiniCom menu item set pulse input parameters The meter IDs of the pulse meters have to be set there as well as the...

Страница 12: ...only the screw on the right side under the KK1 seal user seal of the plastic cover Pull the integrated module forward from the connection The seals in the middle and on the left side may not be remove...

Страница 13: ...the lower 3 and 4 the electric resistance of the extension cable or cables does do not influence the measurement and the reading of the temperatures Material number 28505033 Edition 007 August 2019 Su...

Страница 14: ...Heat Cooling meter integrator PolluTherm Installation and operational instructions M H 6111 INT PolluTherm page 14 Annex 1 Declaration of conformity acc directive 2004 22EC MID...

Отзывы: