Section 9
General
The Aquavar SPD drives are self-diagnosing controllers. If a problem occurs, observe the Status Code Indicator
Light on the front of the unit. No Status Code Indicator Light means either no or low input voltage (less than
140Vac).
DANGER
Status Code Indicator Light is not a voltage indicator! Always turn off disconnect switch and
circuit breaker and wait 5 minutes before servicing. High voltage may still remain on controller.
Refer to the status code label on the side of the controller access cover to diagnose system errors.
See the following diagram.
Use the following table to help troubleshoot problems.
Red Flashes
Fault Code
Restart Action
Constant
Replace Controller
Controller will not restart. Power must be reset to clear the fault.
2 Blinks
No Water / Loss of Prime
Controller will restart automatically according to the No Water Restart
Time switches (switches 3&4 of bank 2).
3 Blinks
Sensor Fault
Controller will restart automatically when the sensor signal is within the
valid operating range.
4 Blinks
Pump or Motor Bound
Controller will restart automatically 5 times. After 5 faults the power
must be reset to clear the fault.
5 Blinks
Short Circuit / Ground Fault
Controller will not restart. Power must be reset to clear the fault.
6 Blinks
Input Phase Loss
Controller will restart automatically 5 times. After 5 faults the power
must be reset to clear the fault.
7 Blinks
Temperature
Controller will restart automatically when temperature is within the
operating range of the controller.
8 Blinks
Over Voltage
Controller will restart automatically when the input voltage is within the
operating range of the controller.
9 Blinks
Motor Overload
Controller will restart automatically.
TROUBLESHOOTING