background image

ADPRO

Network I/O Units – Technical Manual

33355_00

17

Normally open – NEOL
Short circuit = alarm
Open circuit = idle
(Default setting)

Normally open – SEOL
Short circuit = alarm
1K1 = idle
Open circuit = tamper

Normally closed – NEOL
Short circuit = idle
Open circuit = alarm

Normally closed – SEOL
Short circuit = tamper
1K1 = idle
Open circuit = alarm

Normally open – DEOL
Short circuit = tamper
1K1 = alarm
3K3 = idle
Open circuit = tamper

 

 

Normally closed – DEOL
Short circuit = tamper
1K1 = idle
3K3 = alarm
Open circuit = tamper

 

 

Содержание ADPRO 49841000

Страница 1: ...ADPRO Network I O Units For ADPRO NVR Technical Manual March 2018 Doc 33355_00 ...

Страница 2: ......

Страница 3: ...ntain the system Liability You agree to install configure and use the products strictly in accordance with the User Manual and product documents available from Xtralis Xtralis is not liable to you or any other person for incidental indirect or consequential loss expense or damages of any kind including without limitation loss of business loss of profits or loss of data arising out of your use of t...

Страница 4: ...out wheeled bin means that within the European Union the product must be taken to separate collection at the product end of life This applies to the device but also to any accessories marked with this symbol Do not dispose of these products as unsorted municipal waste If you need more information on the collection reuse and recycling systems please contact your local waste administration You can a...

Страница 5: ...e Configurations 9 1 5 Identifying New Units 9 1 6 Specifications Base Unit 9 1 7 Specifications Extension Unit 10 1 8 LED Indicators 10 2 Installation 12 2 1 Connections and Adjustments 12 2 2 Replacing or Removing a Unit 13 2 3 Setting the Base Unit IP Address 14 2 4 Updating the Firmware 15 2 5 Troubleshooting Firmware Updates 16 2 6 Input Circuits 16 3 Frequently Asked Questions 18 ...

Страница 6: ...Network I O Units Technical Manual ADPRO 6 33355_00 ...

Страница 7: ...st system controls the Net I O units through the Ethernet network 10 Mbps network only The base unit offers l 4 monitored or unmonitored inputs for voltage free contacts The possible states are o idle o alarm o tamper short circuit monitored inputs only o tamper open circuit monitored inputs only l 4 relay outputs voltage free switchover contacts with status LED l 3 LED indicators for the system s...

Страница 8: ...ontrolling the unit must be running firmware version XO 4 02 or above l For an extension unit o the extension unit hardware must be version 2 V2 o its base unit must fulfil the requirements as listed above If any of the above requirements is not fulfilled the units will function as the legacy units with unmonitored inputs only 2 states idle alarm The new units are backwards compatible with the leg...

Страница 9: ... this case configure all inputs of the extension units as NEOL For details see Input Circuits on page 16 1 5 Identifying New Units You can easily identify the new units The labels for the new units on the packaging and on the unit itself indicate the new hardware and firmware versions V2 The legacy units do not have these labels Below are examples of new labels A indicates version 2 hardware B ind...

Страница 10: ...LEDs D18 on relay K1 activated D19 on relay K2 activated D20 on relay K3 activated D21 on relay K4 activated The extension unit is set to an address from 0 to 2 using DIP1 Address 3 is not supported by the software For details see Installation on page 12 1 8 LED Indicators The following LED indicators are available on the Net I O units LED Description Green LED on base unit only indicates that the...

Страница 11: ...ADPRO Network I O Units Technical Manual 33355_00 11 Note The three system LEDs power fault and recording are on simultaneously when the unit s IP address is still at the default setting ...

Страница 12: ...stments Caution Before plugging or unplugging any extension units switch off the power to the base unit Plugging or unplugging extension units with power on may result in permanent and irreparable damage to the base and or extension units The table below provides an overview of the connectors ...

Страница 13: ...details see Requirements for Monitored Inputs on page 8 OUT 1 4 Voltage free switchover relay contact outputs Each output has a common terminal C and a normal open NO and normal closed NC terminal DIP1 extension units only DIP switch to set the extension unit address from 0 to 2 address 3 is not supported in the ADPRO NVR software as indicated in the table below The switch for the most significant...

Страница 14: ...three system LEDs on the base unit will light up simultaneously if the unit is still set at the default address The extension units do not have an IP address You assign them an address or sequence number using the DIP switch on the unit For details see Connections and Adjustments on page 12 Use the NetFinder tool to locate all base units on your network and set their IP addresses You can find the ...

Страница 15: ...network segment The firmware update uses the Trivial File Transfer Protocol TFTP Make sure it is enabled on your PC For instructions see Troubleshooting Firmware Updates on page 16 To update the base unit firmware proceed as follows 1 Start NetFinder on your PC 2 Click Search NetFinder will indicate the Net I O units in green 3 Click the desired unit and then click Reboot 4 Select the Force bootlo...

Страница 16: ... NetFinder installed and the base unit must be in the same network segment The PC needs to connect to the base unit but the base unit also needs to communicate back to the PC If updating the firmware fails then check the IP address and subnet mask of both PC and base unit For example the PC with NetFinder has IP address 10 0 0 3 and subnet mask 255 255 0 0 The base unit has IP address 10 0 2 10 an...

Страница 17: ...SEOL Short circuit alarm 1K1 idle Open circuit tamper Normally closed NEOL Short circuit idle Open circuit alarm Normally closed SEOL Short circuit tamper 1K1 idle Open circuit alarm Normally open DEOL Short circuit tamper 1K1 alarm 3K3 idle Open circuit tamper Normally closed DEOL Short circuit tamper 1K1 idle 3K3 alarm Open circuit tamper ...

Страница 18: ... monitored inputs are not available on V3100 devices Monitored inputs require firmware version XO 4 02 or above which is not compatible with the V3100 devices However you can use the new Net I O units with the V3100 device but the inputs will function as unmonitored inputs only I have a spare legacy Net I O unit available Can I use it to replace a faulty new Net I O unit with monitored inputs No T...

Страница 19: ......

Страница 20: ...2223 Middle East 962 6 588 5622 Asia 86 21 5240 0077 Australia and New Zealand 61 3 9936 7000 A Disclaimer about this document statements about Intellectual Property Copyrights and Liability as well as a General Warning are available in an earlier section of this document Document No 33355_00 ...

Отзывы: