ADPRO
Network I/O Units – Technical Manual
33355_00
13
Connector
Description
IP
(base unit only)
Use an Ethernet cable to connect the base unit to the IP network, and (optionally) to
power the unit over Ethernet (PoE).
If using PoE, fix the included clamp on the Ethernet cable inside the mounting box.
Place the clamp as close as possible to the Net I/O unit.
12V
(base unit only)
Optional: if you are using a local power adapter instead of PoE, connect the DC power
wires to the 0V and + terminals. Respect the polarity!
If using a local power adapter, fix the included clamp on the power supply input. Make
one loop inside the clamp.
IN 1–4
Inputs. Each input has its own GND (0V). The inputs function as monitored inputs
(4 states), depending on hardware, firmware, and ADPRO NVR+ firmware version. For
details, see
Requirements for Monitored Inputs
OUT 1–4
Voltage-free switchover relay contact outputs. Each output has a common terminal (C)
and a normal open (NO) and normal closed (NC) terminal.
DIP1
(extension
units only)
DIP switch to set the extension unit address from 0 to 2 (address 3 is not supported in
the ADPRO NVR+ software) as indicated in the table below. The switch for the most
significant bit (MSB) is located
away from the edge
of the unit.
To set address
Set switch
MSB
Other
0
OFF
OFF
1
OFF
ON
2
ON
OFF
Caution!
You can mount the units in a plastic or metal box. If mounting in a metal box: make sure that the metal
box is earthed, and connect the 0V power input terminal of the base unit to the earth.
2.2
Replacing or Removing a Unit
Caution!
Before plugging or unplugging any extension units, switch off the power to the base unit.
Plugging or unplugging extension units with power on may result in
permanent and irreparable
damage
to the base and/or extension units.