ADPRO
Network I/O Units – Technical Manual
33355_00
9
1.4
Possible Configurations
The table below provides an overview of all possible combinations of new and legacy units (base and extension),
and the resulting possibilities for the inputs (monitored or unmonitored):
Base unit
Behaviour inputs on base
unit
Extension unit
Behaviour inputs on
extension unit
Hardware V1
Firmware V1 or V2
Unmonitored (2 states)
Hardware V1 or V2 Unmonitored (2 states)
Hardware V2
Firmware V1
Unmonitored (2 states)
Hardware V1 or V2 Unmonitored (2 states)
Hardware V2
Firmware V2
XO version < 4.02
Unmonitored (2 states)
Hardware V1 or V2 Unmonitored (2 states)
Hardware V2
Firmware V2
XO version ≥ 4.02
Monitored (4 states)
Hardware V1
Unmonitored (2 states)*
Monitored (4 states)
Hardware V2
Monitored (4 states)
(*) In this case, configure all inputs of the extension units as NEOL. For details, see
1.5
Identifying New Units
You can easily identify the new units. The labels for the new units (on the packaging and on the unit itself)
indicate the new hardware and firmware versions (= V2). The legacy units do not have these labels. Below are
examples of new labels:
A = indicates version 2 hardware.
B = indicates version 2 firmware (firmware resides on base unit only).
1.6
Specifications – Base Unit
Power supply
Use a 12 VDC / 350 mA (min.) adapter or PoE switch/injector
Voltage
12 VDC ± 10 %
Current
190 mA max. (all LEDs and relays activated)
140 mA (all relays off)
Inputs
4 monitored or unmonitored inputs for voltage-free contacts: idle, alarm,
tamper short circuit, tamper open circuit (tamper states only on monitored
inputs)
Outputs
4 switchover relay contacts: NC/C/NO, rated 30 VDC @ 1 A
Dimensions
72 mm x 89.7 mm x 62.2 mm
Operating temperature
0–40 °C
Relative humidity
20–93 % (non-condensing)