Codes and technical data
8
F008
Set the stops
frequency
With this parameter you may solve the
problem of no stop due to pipes leaks.
Pay particular attention when
adjusting this parameter since it
may cause frequent pump restarts.
The parameter always
goes at more than 30 Hz.
20Hz ~ 45Hz
25Hz
9
F009
Pressure sensors
selection
it enables to select
the pressure sensor
10bar 16bar 25bar
less than
2.2KW:10bar. more
than 3KW:16bar
10
F010
Overheating
setting
The temperature that triggers the
overheating protection can be set. The
sensor checks the temperature inside
the inverter, and after it has triggered,
it puts it back in operation only when it
has dropped below 20°C
70 ~ 90C°
(if set on H, there is
no protection)
80C°
H cancels the
overheating
protection
11
F011
Main and
supplementary
pumps setting
With this setting you may specify the
pumps sequence when they are in
connected mode (from 1 to 6, with no
repetition). After setting the parameter,
turn off the system for 5 minutes and
then turn it back on. The pump with the
lower number is the main one.
1 ~ 6
1
12
F012
Rotation time
If the operating time coincides with the
one set, the pumps will automatically
alternate
0 ~ 72h
default is 0,
with no rotation
GB