© 2023 by XOLTA
18
Figure 4.1:
Minimum clearance
space on all sides
of a XOLTA BAT-80
• The battery cabinets must be permanently fixed to the underlying foundation. Moving the assembled
battery racks is strictly prohibited as this can damage the rack structure or the battery packs.
Figure 4.2:
Illustration of pre-
mounted base for
XOLTA BAT-80
Outdoor BESS
• All XOLTA Outdoor BESS racks must be placed vertically and safely secured to the rack base and
the underlying foundation.
• The rack base can be pre-mounted on site in parallel with preparing the electrical installation.
NOTE!
Refer to the installation manual for the specification for cable routing placement in the foundation.
10
00
mm
300
mm
200 mm
300 mm
Nothing above
Only free space
Min. 150 mm
Allowed cable
routing space
Содержание BAT-80