© 2023 by XOLTA
21
Figure 4.5:
Cable routing
Table 4.2:
Terminal
functional layout
Figure 4.6:
Power terminals
for BAT-80
4
5
6
7
8
3 2 1
TERMINAL
TERMINAL1
TERMINAL2
TERMINAL3
TERMINAL4
Function
Controller PE
Controller Neutral
Controller power
Inverter PE
Voltage
specification
PE
AC: N
L: 240 VAC
PE
Conductor
cross section
BAT-80 25/30
Max 2.5mm
2
Max 2.5mm
2
Max 2.5mm
2
Max 35mm
2
*)
Conductor
cross section
BAT-80 50/60
Max 2.5mm
2
Max 2.5mm
2
Max 2.5mm
2
Max 16mm
2
*)
TERMINAL
TERMINAL5
TERMINAL6
TERMINAL7
TERMINAL8
Function
Inverter power L1
Inverter power L2
Inverter power L3
Inverter Neutral
Voltage
specification
L1: 400 VAC
L2: 400 VAC
L3: 400 VAC
AC: N
Conductor
cross section
BAT-80 25/30
Max 16mm
2
*)
Max 16mm
2
*)
Max 16mm
2
*)
Max 16mm
2
*)
Conductor
cross section
BAT-80 50/60
Max 35mm
2
*)
Max 35mm
2
*)
Max 35mm
2
*)
Max 35mm
2
*)
*) The terminal block accepts up tp 50mm
2
alu cables, but that will be very difficult to route under/inside the rack.