Ensure the underlaying ground structurally supports the entire
weight of system including foundation.
Refer to manual for requirements on ambient temperature and
corrosive exposure.
Installation Site requirements:
Minimum clearing distances:
• 300 mm sides
• 200 mm between racks
• 1000 mm Front
• 300 mm Back
• Foundation must be level (MAX 0,1
O)
Physical installation requirements:
• Minimum clearance space on all sides of the XOLTA Outdoor
BESS should be observed when planning for installation –
see Figure x for requirements. The required clearances
ensure optimal operation of the thermal management system
and allow adequate space for a technician to service the unit.
NOTE!
that the first rack in a row must have at least 300 mm
free space to the left of the rack when facing the rack. This
allows the door to be opened by at least 150
0
to allow for
servicing of all components.
Please make sure to follow the Site requirements, but always
take local conditions into consideration.
SITE REQUIREMENTS: