Figure 5-27
Positions of the 12 V PSUs
Cable Requirements
●
54 V PSUs
–
When the dual-input mode is selected, the 3000 W PSU is connected to the
C19 connector and is equipped with two C19 cables. The two terminals are
connected to the PDUs of inputs A and B through one cable.
–
When the single-input mode is selected, the 3000 W PSU is connected to
the C19 connector and is equipped with one C19 cable. One terminal is
connected to the PDUs of inputs A and B through one cable.
Take the PSU 3 in the 54 V PSUs as an example. When the dual-input mode is
selected, the front PSU 3 terminals are PSU 3-A and PSU 3-B, as shown in
. PSU 3-A is connected to the PDU of input A through a C19 cable,
and PSU 3-B is connected to the PDU of input B through another C19 cable.
Take the PSU 3 in the 54 V PSUs as an example. When the single-input mode is
selected, the front PSU 3 terminal is PSU 3-A, as shown in
PSU 3-A is connected to the PDU of input A through a C19 cable.
●
12 V PSUs
–
When a PSU of 2000 W or less is used, it is connected to the C13
connector and is equipped with one C13 cable.
–
When a PSU of more than 2000 W is used, it is connected to the C19
connector and is equipped with one C19 cable.
For example, two 12 V PSUs with power of more than 2000 W need to be
configured with two C19 cables. It is recommended that PSU 1 be connected to
the PDU of input A through a C19 cable, and PSU 2 be connected to the PDU of
input B through another C19 cable.