![xFusion Digital Technologies FusionServer G8600 V7 Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/xfusion-digital-technologies/fusionserver-g8600-v7/fusionserver-g8600-v7_manual_3326749059.webp)
Figure 5-28
Connections of PDU connectors
Recommended Solution for Typical Configurations
shows the recommended PSU configuration solutions when the server is
configured with two types of GPUs.
Table 5-14
Recommended solutions
A100 GPU module (HGX A100 8-GPU) H100 GPU module (HGX H100 8-GPU)
Recommended cabinet power
consumption: 8.5 kW
Recommended cabinet power
consumption: 12 kW
Power consumption of the entire
system: 6.5 kW
Power consumption of the entire
system: 10 kW
Recommended PSU configurations:
Two 12 V 2000 W PSUs (1+1
redundancy)
Four 54 V 3000 W PSUs (2+2
redundancy, single-input mode)
Recommended PSU configurations:
Two 12 V 3000 W PSUs (1+1
redundancy)
Four 54 V 3000 W PSUs (3+1
redundancy, dual-input mode)
Power cables:
2 x C13 4 x C19 cables
Power cables:
10 x C19 cables
FusionServer G8600 V7 Server