Item
Specifications
Operating altitude
≤ 3050 m
● When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature
decreases by 1ºC (1.8ºF) for every increase of 300 m
(984.24 ft).
● When the server configuration complies with ASHRAE
Class A3 and the altitude is above 900 m (2952.76 ft),
the highest operating temperature decreases by 1ºC
(1.8ºF) for every increase of 175 m (574.15 ft).
● HDDs cannot be used at an altitude of over 3050 m
(10,006.56 ft).
Corrosive gaseous
contaminant
Maximum growth rate of the corrosion product thickness:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
Particle contaminant
● Meets the requirements of ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the equipment
room be monitored by a professional agency.
Noise
The declared A-weighted sound power levels (LWAd)
and declared average bystander position A-weighted
sound pressure levels (LpAm) listed are measured at
23ºC (73.4ºF) in accordance with ISO 7779 (ECMA 74)
and declared in accordance with ISO 9296 (ECMA 109).
● Idle:
– LWAd: 7.15 Bels
– LpAm: 55.2 dBA
● Operating:
– LWAd: 7.18 Bels
– LpAm: 55.5 dBA
NOTE
Actual sound levels generated during operation vary depending
on the configuration, load, and ambient temperature.
FusionServer G8600 V7 Server
Technical White Paper
6 Product Specifications
Issue 03 (2023-09-15)
Copyright © xFusion Digital Technologies Co., Ltd.
69