5.2.3.3. A reinforced concrete slab may be required under the
tank as a foundation in the excavation where the bottom is
unstable.

5.3. GEOTEXTILE

5.3.1. The tank owner or the owner’s technical representative is
responsible for determining whether a geotextile or an alternate
filtering technique is appropriate for a specific installation.
Geotextile allows the passage of water, but prevents the
migration and mixing of in situ soil and the select backfill
material. Geotextile helps preserve the integrity of the select
backfill envelope, which surrounds and supports the tank.

5.3.2. Xerxes recommends that geotextile be used when the
tank is installed in:
• areas with frequently changing groundwater conditions or

areas subject to tidal fluctuations,

• unstable soils such 

as cited in SECTION 5.2.3,

• water conditions with silty in situ soil.

5.3.3. For further information concerning geotextile specifica-
tions and installation procedures, consult the geotextile
supplier’s installation guidelines or instructions.

5.3.4. Polyethylene film is not considered an effective geotextile
material. It may tear or degrade while in service.

6. ANCHORING TANKS

Xerxes recommends that all tanks be anchored in installa-
tions in which the tank could be exposed to water. Xerxes
recommends that every site be thoroughly evaluated for the
potential of a rise in the local water table or of trapped
water. Failure to anchor a tank under these conditions may
damage the tank or surrounding property. 

6.1. DEADMAN ANCHORS

6.1.1. A deadman is typically a reinforced concrete beam. 

6.1.2. The length of the deadman is typically equal to the length
of the tank.

6.1.3. A deadman may be fabricated in multiple sections as long
as the total length is not decreased and each section contains at
least two balanced anchor points. 

6.1.4. The width and thickness of the deadmen depend on the
tank diameter, water-table height, number of attached collar
risers and burial depth.

6.1.5.  Deadmen should be designed according to the American
Concrete Institute (ACI) code. 

6.1.6. 

Refer to TABLE 6-1

for typical deadmen dimensions given

the situation of an empty tank with a burial depth of 3 feet, with
groundwater to grade and with one attached collar riser.

13

5.2.2.2. If more than one tank is to be installed in the same hole,
allow for at least 18 inches between the tanks.

(See FIGURE 5-4.

)

FIGURE 5-4

5.2.3. UNSTABLE IN SITU SOIL CONDITIONS

Xerxes recommends that the tank owner seek the advice of
a local foundation professional engineer if the in situ soil is
extremely soft or inherently unstable (for example, peat,
quicksand, muck, landfill, very soft or highly expansive
clay, underground stream, etc.).

5.2.3.1. If the soil has less than 750 lbs./sq. ft. cohesion as
calculated from an unconfined compression test; or in soils
having an ultimate bearing capacity of less than 3,500 lbs./sq.
ft.; or where soil will not maintain a vertical wall, the excavation
must allow a minimum space equal to half the diameter of the
tank between the excavation wall and both the side and the endcap
of the tank, to enhance lateral resistance. 

(See FIGURE 5-5.)

5.2.3.2. The spacing between adjacent tanks is to be at least 18
inches. 

(See FIGURE 5-5.)

FIGURE 5-5

1/2

Tank

Dia.

18"

1/2 Tank Dia.

1/2 Tank Dia.

Unstable Soil

18”

18”

18”

18”

18”

Stable Soil

Содержание Fiberglass Underground Storage Tanks

Страница 1: ...Installation Manual and Operating Guidelines For Single Wall and Double Wall Fiberglass Underground Storage Tanks Owner should retain this manual for reference to operating guidelines...

Страница 2: ...allationTesting p 18 9 1 General Section 10 Ballasting p 19 10 1 General Section 11 Piping andVenting p 19 11 1 Internal Piping 11 2 External Piping 11 3 Venting Tank 11 4 Venting Interstitial Space S...

Страница 3: ...6 Careless activity or reckless operation of equipment can cause death serious injury or property damage 1 2 GENERAL 1 2 1 It is important to follow the procedures and instructions in this manual in o...

Страница 4: ...uated on top of the tank in its upright position FIGURE 2 1 30 Max 1 2 8 Federal state and local codes and regulations always take precedence over a Xerxes requirement 1 2 9 Xerxes must authorize in w...

Страница 5: ...too much momentum Momentum can grow because fittings on top of the tank make it top heavy Make sure the tank s fittings and manways never touch the ground Do not rotate the tank more than 120 from the...

Страница 6: ...serious injury 3 1 9 Refer to the appropriate section below for instructions for the following situations 3 1 9 1 For testing a single wall tank see SECTION 3 2 3 1 9 2 For testing a double wall tank...

Страница 7: ...terstitial space by itself may damage the primary tank or cause tank failure 3 3 3 2 Free the hose from the service fitting by cutting the nylon tie 3 3 3 3 Insert the hose into the quick disconnect f...

Страница 8: ...ct the air supply line 3 4 1 9 Soap all service fittings and manways Watch for active air bubbles which indicate a leak Look through the laminate for any active air bubbles rising to the top Their pre...

Страница 9: ...eeded for the test manifolds Follow instructions in Point 3 1 5 See FIGURE 3 6 and FIGURE 3 7 3 6 1 3 Before doing the air test of the base tank described in SECTION 3 6 2 and the air test of the end...

Страница 10: ...r End Tank End Tank End Tank Lifting Lug Typical Manway with Fittings Optional Reservoir Monitor Fitting Base Tank 9 FIGURE 3 12 FIGURE 3 13 3 7 2 AIR TEST OF BASE TANK 3 7 2 1 Connect the pressure so...

Страница 11: ...Disconnect the air supply line 3 8 3 4 Soap all service fittings and manways Watch for active air bubbles which indicate a leak Look through the laminate for any active air bubbles rising to the top T...

Страница 12: ...d result in death or serious injury 5 1 GENERAL 5 1 1 The installing contractor must take all precautions necessary to protect employees working in or near a tank excavation These precautions should i...

Страница 13: ...vide sufficient clearance to allow the deadmen to be set outside of the tank shadow See FIGURE 5 3 FIGURE 5 3 5 2 2 STABLE IN SITU NATIVE SOIL CONDITIONS 5 2 2 1 Where shoring is not required to maint...

Страница 14: ...ced concrete beam 6 1 2 The length of the deadman is typically equal to the length of the tank 6 1 3 A deadman may be fabricated in multiple sections as long as the total length is not decreased and e...

Страница 15: ...for further information 6 1 8 Lay the deadmen in the excavation parallel to the tank and outside of the tank shadow See FIGURE 5 3 6 1 9 In multiple tank installations with deadmen each tank will have...

Страница 16: ...must be used on all marked hold down locations Do not place straps between ribs except on 4 foot diameter tanks Failure to properly place straps may result in tank damage 6 4 4 Data for hold down stra...

Страница 17: ...p as near the loop or thimble as possible turn nuts on second clip firmly but do not tighten initially See FIGURE 6 4 6 5 15 When more than two clips are required space additional clips equally betwee...

Страница 18: ...ce one 12 inch lift of approved backfill material evenly around the tank From the edge of the hole or the top of an adjacent tank push the backfill in place by using a nonmetal probe long enough to re...

Страница 19: ...osed areas of the tank and all fittings and monitoring the pressure for one hour 9 1 4 Carefully relieve the pressure in the tank Remove the quick disconnect assembly from dry double wall tanks 12 Do...

Страница 20: ...inches 6 inches for 12 foot diameter tanks from the tank bottom All metal fittings and other metal components must be coated to protect against corrosion 11 1 2 Refer to FIGURE 11 1 along with TABLE 1...

Страница 21: ...d in SECTION 5 13 1 6 When the tank has been backfilled to subgrade before placement of asphalt or concrete take a measurement of the internal diameter of the tank See SECTION 14 of the Installation M...

Страница 22: ...4 3 1 Place the dipstick into a service fitting with a standpipe 14 3 2 Measure and record the distance from the tank bottom to the top of the standpipe 14 3 3 Pull the dipstick up until the nail catc...

Страница 23: ...l the UST coordinator at the Xerxes plant nearest you 15 4 1 6 If a tank is sloped the reservoir should be at the high end 15 4 1 7 In a tank with the interstice filled with monitoring fluid Xerxes re...

Страница 24: ...and vapors Do not pressurize the ACR assembly after installation is completed The ACR system is an enclosed space Hazardous fumes may be present so precautions should be taken to properly vent the sp...

Страница 25: ...ion process 16 5 3 TESTING ACR WT RISER TOP 16 5 3 1 Water test the riser top after the adhesive sealant in the groove at the top of the riser has sufficiently set 16 5 3 2 Plug any wall penetrations...

Страница 26: ...The contractor must install a concrete form to allow a minimum 3 inch clearance between the concrete pad street box frame and the riser top 16 7 3 Backfill to the top of the ACR system 16 7 4 Backfil...

Страница 27: ...ion such as automatic shut off devices flapper valves or vent restriction devices ball float valves which will close off the internal piping and reduce the tank s capacity 18 2 5 Owner operator must n...

Страница 28: ...ice TRUCHEK Hydrostatic Monitoring System brochure 20 1 1 2 Among those materials available from technical support at Xerxes Minneapolis are Alternate Backfill Supplemental Instructions UST Deep Buria...

Страница 29: ...d according to installation instructions B InternalDiameterMeasurement Theinternaldiameterofthetankismeasuredanddocumented FinalInternalDiameterinSection4below C Monitoring Fluid Tanks 1 Check and rec...

Страница 30: ...369 10 4 10 4 21 5 1 4 21 5 1 4 3 200 4 500 6 200 12 000 12 068 11 849 10 4 10 4 24 1 4 24 1 4 3 600 5 000 7 000 15 000 15 248 14 976 10 4 10 4 29 5 3 4 29 5 3 4 4 500 6 100 8 600 10 20 000 20 055 19...

Страница 31: ...Iowa Phone 563 886 6172 Fax 563 886 2042 Corporate Office 7901 Xerxes Avenue South Minneapolis MN 55431 Phone 952 887 1890 Fax 952 887 1870 www xerxescorp com Manufacturing Facilities 2001 Xerxes Corp...

Отзывы: