background image

10

3.7.4.2. Add air as required and stabilize the air pressure in the
total tank system to 5 psig.

3.7.5. EXTERNAL SOAP TEST

3.7.5.1. Soap the entire exterior of the tank, checking for leaks.

(Follow instructions in Points 3.1.6. through 3.1.8., 

including

Warnings following 3.1.8.) Watch for active air bubbles, which
indicate a leak. Pay special attention to fittings and manways.

3.7.5.2. Monitor the pressure for one hour. 

3.7.5.3. When the test is completed, carefully release the air
pressure from the tank by opening the air-supply valve.

3.7.5.4. When the airflow stops, remove the test manifold.

3.7.5.5. Replace the protective covers in the service fittings.

3.8. TESTING A DOUBLE-WALL MULTICOMPARTMENT
TANK WITH A WET INTERSTITIAL SPACE

Never pressurize a wet interstitial space. Doing so may
damage the primary tank or cause tank failure.

3.8.1. GENERAL

3.8.1.1.

See FIGURE 3-10 and FIGURE 3-11

.

3.8.2. BASE TANK’S PRIMARY (INTERNAL) TANK

3.8.2.1. Keep the tank vertical (the reservoir on top) at all times
or the monitoring fluid may drain from the reservoir.

3.8.2.2. Remove all temporary service-fitting plugs and the
reservoir-fitting plug. 

3.8.2.3. Check the monitoring-fluid level in the reservoir. It
should be about 1/4 full.

3.8.2.4. Visually check the interior of each compartment for
monitoring fluid.

There should not be any. 

3.8.2.5. Redope fittings and install plugs in all openings, except
one service fitting in each compartment (needed for the test
manifolds) and the reservoir fitting. 

Follow instructions in Point

3.1.5. (See FIGURE 3-6 and FIGURE 3-7.)

3.8.2.6. Before doing the air test of the base tank 

(described in

SECTION 3.8.3.) 

and the air test of the end tank(s) 

(described in

SECTION 3.8.4.)

, install a test manifold in the open service

fitting on both the base and end tank(s).

3.8.3. AIR TEST OF BASE TANK’S PRIMARY TANK 

3.8.3.1. Connect the pressure source to the test manifold on the
base tank. 

(See FIGURE 3-3 and FIGURE 3-11.)

3.8.3.2. Pressurize the primary tank of the base tank to 5 psig.
Allow the pressure to stabilize by adding or removing air as
necessary. 

3.8.3.3. Close the air-supply valve on the test manifold on the
base tank. Disconnect the air-supply line.

3.8.3.4. Soap all service fittings and manways. Watch for active
air bubbles, which indicate a leak. Look through the laminate for
any active air bubbles rising to the top.Their presence would
indicate an internal leak. Also, check the reservoir for bubbles in
the monitoring fluid. 

(The monitoring-fluid level will rise

during the air test.)

3.8.3.5. Monitor the pressure for one hour. 

Do not release air

pressure.

3.8.4. AIR TEST OF END TANK(S)’ PRIMARY TANK(S) 

3.8.4.1. Connect the pressure source to the test manifolds on
the end tank(s). 

(See FIGURE 3-3 and FIGURE 3-12.)

3.8.4.2. Pressurize the primary tank of the end tank(s) to 5 psig.
Allow the pressure to stabilize by adding or removing air as
necessary. 

Note:  The monitoring-fluid level will rise during the air test. 

3.8.4.3. Close the air-supply valve on the test manifolds on the
end tanks. Disconnect the air-supply line.

3.8.4.4. Soap all service fittings and manways. Watch for active
air bubbles, which indicate a leak. Check the reservoir for
bubbles in the monitor fluid.

(The level of the monitor fluid will

naturally rise due to the pressure in the primary tank.) 

3.8.4.5. Monitor the pressure for one hour.

3.8.4.6. When the test is complete, carefully release the air
pressure from all compartments by opening the air-supply valve.

3.8.4.7. When the air flow stops, remove the test manifolds.

3.8.4.8. Check the monitoring-fluid level in the reservoir. It
should be at approximately the same level as the pretest level. 

3.8.5. SECONDARY TANK (EXTERNAL)

Do not connect air supply directly to the interstitial-space
monitor fitting. Pressurizing the secondary tank (interstitial
space) by itself may damage the primary tank or cause tank
failure.

3.8.5.1. Check the exterior of the tank for monitoring fluid.
(The monitoring fluid is dyed blue to distinguish between
moisture and monitoring fluid.) If monitoring fluid is found, wipe
the tank dry and verify that the monitoring fluid does not
reappear. Lift the tank to check the bottom. 

Do not roll the tank.

3.8.5.2. Visually check the interior of the tank for monitoring
fluid. 

There should not be any.

3.8.5.3. Replace the protective covers in the service fittings and
the reservoir fitting.

4. BACKFILL MATERIAL

4.1. GENERAL

4.1.1. Xerxes tanks must be installed using either pea gravel or
crushed stone as backfill material.

Содержание Fiberglass Underground Storage Tanks

Страница 1: ...Installation Manual and Operating Guidelines For Single Wall and Double Wall Fiberglass Underground Storage Tanks Owner should retain this manual for reference to operating guidelines...

Страница 2: ...allationTesting p 18 9 1 General Section 10 Ballasting p 19 10 1 General Section 11 Piping andVenting p 19 11 1 Internal Piping 11 2 External Piping 11 3 Venting Tank 11 4 Venting Interstitial Space S...

Страница 3: ...6 Careless activity or reckless operation of equipment can cause death serious injury or property damage 1 2 GENERAL 1 2 1 It is important to follow the procedures and instructions in this manual in o...

Страница 4: ...uated on top of the tank in its upright position FIGURE 2 1 30 Max 1 2 8 Federal state and local codes and regulations always take precedence over a Xerxes requirement 1 2 9 Xerxes must authorize in w...

Страница 5: ...too much momentum Momentum can grow because fittings on top of the tank make it top heavy Make sure the tank s fittings and manways never touch the ground Do not rotate the tank more than 120 from the...

Страница 6: ...serious injury 3 1 9 Refer to the appropriate section below for instructions for the following situations 3 1 9 1 For testing a single wall tank see SECTION 3 2 3 1 9 2 For testing a double wall tank...

Страница 7: ...terstitial space by itself may damage the primary tank or cause tank failure 3 3 3 2 Free the hose from the service fitting by cutting the nylon tie 3 3 3 3 Insert the hose into the quick disconnect f...

Страница 8: ...ct the air supply line 3 4 1 9 Soap all service fittings and manways Watch for active air bubbles which indicate a leak Look through the laminate for any active air bubbles rising to the top Their pre...

Страница 9: ...eeded for the test manifolds Follow instructions in Point 3 1 5 See FIGURE 3 6 and FIGURE 3 7 3 6 1 3 Before doing the air test of the base tank described in SECTION 3 6 2 and the air test of the end...

Страница 10: ...r End Tank End Tank End Tank Lifting Lug Typical Manway with Fittings Optional Reservoir Monitor Fitting Base Tank 9 FIGURE 3 12 FIGURE 3 13 3 7 2 AIR TEST OF BASE TANK 3 7 2 1 Connect the pressure so...

Страница 11: ...Disconnect the air supply line 3 8 3 4 Soap all service fittings and manways Watch for active air bubbles which indicate a leak Look through the laminate for any active air bubbles rising to the top T...

Страница 12: ...d result in death or serious injury 5 1 GENERAL 5 1 1 The installing contractor must take all precautions necessary to protect employees working in or near a tank excavation These precautions should i...

Страница 13: ...vide sufficient clearance to allow the deadmen to be set outside of the tank shadow See FIGURE 5 3 FIGURE 5 3 5 2 2 STABLE IN SITU NATIVE SOIL CONDITIONS 5 2 2 1 Where shoring is not required to maint...

Страница 14: ...ced concrete beam 6 1 2 The length of the deadman is typically equal to the length of the tank 6 1 3 A deadman may be fabricated in multiple sections as long as the total length is not decreased and e...

Страница 15: ...for further information 6 1 8 Lay the deadmen in the excavation parallel to the tank and outside of the tank shadow See FIGURE 5 3 6 1 9 In multiple tank installations with deadmen each tank will have...

Страница 16: ...must be used on all marked hold down locations Do not place straps between ribs except on 4 foot diameter tanks Failure to properly place straps may result in tank damage 6 4 4 Data for hold down stra...

Страница 17: ...p as near the loop or thimble as possible turn nuts on second clip firmly but do not tighten initially See FIGURE 6 4 6 5 15 When more than two clips are required space additional clips equally betwee...

Страница 18: ...ce one 12 inch lift of approved backfill material evenly around the tank From the edge of the hole or the top of an adjacent tank push the backfill in place by using a nonmetal probe long enough to re...

Страница 19: ...osed areas of the tank and all fittings and monitoring the pressure for one hour 9 1 4 Carefully relieve the pressure in the tank Remove the quick disconnect assembly from dry double wall tanks 12 Do...

Страница 20: ...inches 6 inches for 12 foot diameter tanks from the tank bottom All metal fittings and other metal components must be coated to protect against corrosion 11 1 2 Refer to FIGURE 11 1 along with TABLE 1...

Страница 21: ...d in SECTION 5 13 1 6 When the tank has been backfilled to subgrade before placement of asphalt or concrete take a measurement of the internal diameter of the tank See SECTION 14 of the Installation M...

Страница 22: ...4 3 1 Place the dipstick into a service fitting with a standpipe 14 3 2 Measure and record the distance from the tank bottom to the top of the standpipe 14 3 3 Pull the dipstick up until the nail catc...

Страница 23: ...l the UST coordinator at the Xerxes plant nearest you 15 4 1 6 If a tank is sloped the reservoir should be at the high end 15 4 1 7 In a tank with the interstice filled with monitoring fluid Xerxes re...

Страница 24: ...and vapors Do not pressurize the ACR assembly after installation is completed The ACR system is an enclosed space Hazardous fumes may be present so precautions should be taken to properly vent the sp...

Страница 25: ...ion process 16 5 3 TESTING ACR WT RISER TOP 16 5 3 1 Water test the riser top after the adhesive sealant in the groove at the top of the riser has sufficiently set 16 5 3 2 Plug any wall penetrations...

Страница 26: ...The contractor must install a concrete form to allow a minimum 3 inch clearance between the concrete pad street box frame and the riser top 16 7 3 Backfill to the top of the ACR system 16 7 4 Backfil...

Страница 27: ...ion such as automatic shut off devices flapper valves or vent restriction devices ball float valves which will close off the internal piping and reduce the tank s capacity 18 2 5 Owner operator must n...

Страница 28: ...ice TRUCHEK Hydrostatic Monitoring System brochure 20 1 1 2 Among those materials available from technical support at Xerxes Minneapolis are Alternate Backfill Supplemental Instructions UST Deep Buria...

Страница 29: ...d according to installation instructions B InternalDiameterMeasurement Theinternaldiameterofthetankismeasuredanddocumented FinalInternalDiameterinSection4below C Monitoring Fluid Tanks 1 Check and rec...

Страница 30: ...369 10 4 10 4 21 5 1 4 21 5 1 4 3 200 4 500 6 200 12 000 12 068 11 849 10 4 10 4 24 1 4 24 1 4 3 600 5 000 7 000 15 000 15 248 14 976 10 4 10 4 29 5 3 4 29 5 3 4 4 500 6 100 8 600 10 20 000 20 055 19...

Страница 31: ...Iowa Phone 563 886 6172 Fax 563 886 2042 Corporate Office 7901 Xerxes Avenue South Minneapolis MN 55431 Phone 952 887 1890 Fax 952 887 1870 www xerxescorp com Manufacturing Facilities 2001 Xerxes Corp...

Отзывы: