Preparing For Installation
20
XPLORE 120/12 Battery Charger Owner's Guide
For example:
n
In US NEC, you may use a 14 AWG wire with a 15 A
breaker for up to 12 A continuous current (or 12 AWG for a
20 A breaker for up to 16 A continuous current)
n
Note that every jurisdiction will have different requirements
as will each application, so research the regulations for
your local jurisdiction to determine which wire size and
type is correct based on the maximum AC input current
marked on the chargers and given in
Other examples of AC wiring requirements:
Conductors and flexible cords shall be stranded copper for the
marine environment.
The AC (mains) wiring supplying the XPLORE Charger must be
protected by the correct size and type of branch-circuit rated fuse
or breaker to meet the applicable installation codes. If a fuse is
used instead of a breaker, a correctly rated disconnect switch is
required ahead of the fuse so that power can be turned off,
allowing fuse replacement and safe maintenance of other
equipment on the mains circuit.
Additionally, an AC junction box must be installed next to the
XPLORE Charger. See
below.
Figure 8 Junction box placement
The top picture is typical in North American applications. The
bottom picture is typical in IEC jurisdictions.
Содержание XPLORE 120A 12V
Страница 1: ...XPLORE 120A 12V Battery Charger Owner s Guide Model XPLORE 120 12 Battery Charger 819 0120 12...
Страница 12: ...This page is intentionally left blank 2...
Страница 18: ...This page is intentionally left blank 2...
Страница 24: ...This page is intentionally left blank 2...
Страница 60: ...This page is intentionally left blank 2...
Страница 72: ...975 1038 01 01 Rev C 31021 http www xantrex com 1 800 670 0707 1 408 987 6030 Printed in...