Freedom X Owner’s Guide

Inverter Applications

The Freedom X performs differently depending on the AC loads 
connected to it. If you are having problems with any of your loads, 
read this section.

Resistive Loads

These are the loads that the inverter finds the simplest and most 
efficient to drive. Voltage and current are in phase (that is, in step 
with one another). Resistive loads usually generate heat in order to 
accomplish their tasks. Toasters, coffee pots, and incandescent 
lights are typical resistive loads. It is usually impractical to run 
larger resistive loads—such as electric stoves and water heaters—
from an inverter due to their high current requirements. Even 
though the inverter can most likely accommodate the load, the size 
of battery bank required would be impractical if the load is to be run 
for long periods.

Motor Loads

Induction motors (that is, motors without brushes) require two to six 
times their running current on start up. The most demanding are 
those that start under load, for example, compressors and pumps. Of 
the capacitor start motors (typical in drill presses, band saws, etc), 
the largest you can expect to run is ½ hp (the transfer relays are 
rated at 2 hp). Universal motors are generally easier to start. Since 
motor characteristics vary, only testing will determine whether a 
specific load can be started and how long it can be run.
If a motor fails to start within a few seconds or loses power after 
running for a time, it should be turned off. When the inverter 
attempts to start a load that is greater than it can handle, it will turn 
itself off after a few seconds.

Long Transfer Times 

The Freedom X may take a long time 

(~ 0.1–0.2 seconds) to transfer to Battery Mode when shore power 
is cut off while powering a motor load. Motor loads typically 
“freewheel” when power is removed (for example, a grinder) and 
causes a longer transfer time. The longer transition from shore 
power to inverter power may cause connected computers or other 
sensitive equipment to operate incorrectly. To avoid this effect, do 
not connect motor loads together with sensitive equipment to the 
inverter for power.

Freedom X Owners Guide.book  Page 60  Wednesday, May 11, 2016  10:32 AM

Содержание Freedom X 1200 120VAC

Страница 1: ...TM TM Freedom X Sine Wave Inverter Owner s Guide Product Part Number 806 1212 Freedom X Owners Guide book Page i Wednesday May 11 2016 10 32 AM...

Страница 2: ...Freedom X Owners Guide book Page ii Wednesday May 11 2016 10 32 AM...

Страница 3: ...PS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION THE ACCURACY CANNOT BE GUARANTEED APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT HTTP WWW XANTREX COM...

Страница 4: ...m X Sine Wave Inverter Abbreviation or Acronym A Amps AC Alternating Current DC Direct Current in lbf inch pounds or pound force a unit of torque kW Kilowatts 1000 watts LBCO Low Battery Cutout or Cut...

Страница 5: ...electrical hazard exists which will result in personal injury if the instructions are not followed This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey al...

Страница 6: ...er all power is disconnected 7 To reduce the risk of electrical shock disconnect both AC and DC power from the inverter before attempting any maintenance or cleaning or working on any components conne...

Страница 7: ...Unit s components may produce arcs or sparks Do not install near batteries in machinery space or in an area in which ignition protected equipment is required 975 0767 01 01 v Areas include any space...

Страница 8: ...on the engine 2 Freedom X inverter products are designed for deep cycle lead acid batteries See warning below when connecting to lithium ion batteries 3 Do not use transformerless battery chargers in...

Страница 9: ...cid contacts skin or clothing wash immediately with soap and water If acid enters your eye immediately flood it with running cold water for at least twenty minutes and have someone within range of you...

Страница 10: ...o be used for mobile or commercial applications This Inverter is designed for marine applications only when additional drip protection is installed in certain orientations See the section on Specifica...

Страница 11: ...not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encour...

Страница 12: ...Freedom X Owners Guide book Page x Wednesday May 11 2016 10 32 AM...

Страница 13: ...es 9 Marine Installation 34 Freedom X Inverter Configuration 37 Freedom Inverter Operation 47 Operating During Transition Between AC Mode and Battery Mode 50 Troubleshooting 53 Warning Messages 54 Tro...

Страница 14: ...Freedom X Owners Guide book Page ii Wednesday May 11 2016 10 32 AM...

Страница 15: ...eedom X base package includes the following items one Freedom X unit one Owner s Guide and extra safety labels one set of pre installed M8 DC terminal nuts not shown one DC ground box lug NOTE If any...

Страница 16: ...battery shutdown for the inverter can be manually selected by the user from 10 5 to 12 1 VDC Low Voltage Shutdown Delay Timer Configurable from 1 to 300 seconds to reduce an unnecessary shutdown of i...

Страница 17: ...exceeded See page 56 for precautions Ignition Control The Freedom X provides two user selectable options for ignition control Ignition Auto on The Freedom X can automatically turn the inverter on and...

Страница 18: ...d GFCI 2 ACC input terminal for connecting ignition control wiring 3 RJ12 port allows you to connect an accessory remote control device 4 Mounting flanges on both sides allow you to mount the inverter...

Страница 19: ...t point up or down Cooling fans turn on when powering loads above 500 watts or when the internal temperature reaches a set point temperature Display Panel Batt MODE AC MODE VAC VAC OUTPUT INPUT 888 88...

Страница 20: ...2 4 Feature Description 1 DC Compartment Cover protects the DC compartment from debris and keeps the DC cables secure Using the captive nut panel screw the cover can be opened and lifted out during wi...

Страница 21: ...secure all AC and DC disconnect devices and automatic generator starting devices Installation Codes Governing installation codes vary depending on the specific location and application of the installa...

Страница 22: ...riately for load and application strain relief clampsb for the AC knockouts Wire nuts or crimp connectors for AC wire and appropriate tools DC cable sized appropriately for load and application Lugs f...

Страница 23: ...divided into these main steps Step 1 Designing the Installation on page 10 Step 2 Choosing a Location for the Unit on page 15 Step 3 Mounting the Unit on page 16 Step 4 Connecting the AC Input Wires o...

Страница 24: ...other in a typical recreational vehicle or fleet vehicle installation Also see Marine Installation on page 34 Figure 1 Typical Recreational Vehicle and Fleet Vehicle Installation C Fuse disconnect or...

Страница 25: ...uses and disconnect devices AC Input The circuit breaker or fuse connected through hard wiring that is used to supply the Freedom X must be rated at no more than 30A and must be approved for use on 12...

Страница 26: ...n codes usually specify solid or stranded overall size of the conductors and type and temperature rating of the insulation around the wire Cord must be of type S SE SEOO SO ST STO SJ SJE SJEOO SJT or...

Страница 27: ...al wires All connections to the unit should comply with all local codes and ordinances DC Cabling This includes all the cables and connectors between the batteries the DC disconnect and over current p...

Страница 28: ...atched to the size of cables used in accordance with the applicable installation codes The breaker or disconnect and fuse should be located as close as possible to the battery in the positive cable Ap...

Страница 29: ...d Allow at least 5 inches of clearance at the DC end of the Freedom X for air flow 1 inch on each side and 2 inches at the AC end The more clearance for ventilation around the unit the better the perf...

Страница 30: ...5 for drip shield installation on Marine applications B C Under a horizontal surface see A In a horizontal position on a vertical surface see B On a horizontal surface see C 3 Mark the desired number...

Страница 31: ...or larger For recommended equipment ground cable size see below Table 3 Recommended Equipment Ground Cable size Application Minimum equipment ground cable size Stranded cable is recommended Recreation...

Страница 32: ...connect the inverter to an existing AC installation and then plug loads into GFCI receptacles connected to that circuit If you plan to use the Freedom X with a customer supplied GFCI installed on the...

Страница 33: ...input and AC output connections observe the correct color code for the appropriate AC wire as described below in Table 5 Table 5 Color codes for typical AC wiring Color AC Wire Black Red Line White bl...

Страница 34: ...and lifting the cover up and out captive nut panel screw 4 Strip a single AC input wire as appropriate 5 Remove the knockout and install a strain relief clamp 6 Route the wires through the strain rel...

Страница 35: ...the spring clamp to secure the wire Alternatively if the unit is equipped with screw terminals tighten the screw to secure the wire 11 Repeat previous steps 8 through 10 for Ground G and Neutral N co...

Страница 36: ...round Fault Circuit Interrupters GFCIs on page 14 WARNING FIRE SHOCK AND ENERGY HAZARDS Make sure wiring is disconnected from all electrical sources before handling All wiring must be done in accordan...

Страница 37: ...the strain relief clamp not shown in the figure 7 Locate the Line Ground and Neutral terminals on the AC OUT terminal labeled as L G and N respectively 8 If you are installing a GFCI device proceed to...

Страница 38: ...the two screws holding it in place 2 Set the two screws aside 3 Push the GFCI cover plate in and remove it from the AC compartment 4 Install the GFCI device according to its wiring diagram shown on t...

Страница 39: ...Splice three white Neutral wires together using a twist on wire connector the other end of the white AC wire in step 9 the other end of the white AC wire in step 10 and the AC Output Neutral wire 12...

Страница 40: ...egrade the inverter s ability to operate the loads Figure 4 shows the DC end for your reference Figure 4 DC End POSITIVE NEGATIVE DC Ground Stud NOTICE REVERSE POLARITY DAMAGE Check cable polarity at...

Страница 41: ...to the inverter cable The amount stripped off will depend on the terminals chosen 7 Attach the cable lug that will join the cable to the inverter DC terminal Cover the lug stem with heat shrink insula...

Страница 42: ...ly Loose connections cause excessive voltage drop and may cause overheated wires and melted insulation Do not over tighten the nut on the DC input terminals Damage to the DC input terminals may result...

Страница 43: ...ng bus point as required by electrical regulations Use copper wire that is either bare or provided with green insulation Use the provided DC ground box lug to connect the ground wire and onto the DC g...

Страница 44: ...is feature can avoid unnecessary battery drain that would otherwise occur if the inverter was operated without a charging source such as the vehicle alternator To enable ignition control 1 Ensure that...

Страница 45: ...allows the inverter to operate Battery mode automatically when an ignition control wire is connected to the ACC input and a valid ignition signal is constantly detected The inverter works in tandem w...

Страница 46: ...shore power is not present 2 Press the inverter Power button to turn the inverter on The green LED indicating Battery mode Inverter mode turns on and the LCD screen displays the BATT MODE icon 3 Plug...

Страница 47: ...the Freedom X will automatically supply the appliances with inverter power if the shore power source fails or becomes disconnected If the inverter Power button on the Freedom X is turned ON and shore...

Страница 48: ...with branch circuit breakers that supply only loads that run off the Freedom X 4 Engine negative bus DC ground bus 5 DC power supplied by a battery bank and protected by a DC fuse in the positive cab...

Страница 49: ...o contact with the Freedom X You may purchase the drip shield set by contacting customer support When ordering mention part number 808 1050 Figure 8 Drip Shields Drip Shield set part 808 1050 Differen...

Страница 50: ...he drip shields above the Freedom X making sure you cover the entire width of the unit You can overlay the shields as shown in Figure 9 below 3 Fasten the screws through the holes in the drip shield i...

Страница 51: ...MODE VAC VAC OUTPUT INPUT 120 120 120 volts AC 120 volts AC AC mode icon 75 100 0 25 In Battery Mode also called Inverter Mode the AC output power comes from the battery The LCD Screen switches to dis...

Страница 52: ...ry Voltage Battery Discharge Current Batt MODE VAC VAC OUTPUT INPUT 131 0 Load Percent Batt MODE VAC VAC OUTPUT INPUT 131 20 Warning Fault VAC VAC OUTPUT INPUT 131 e02 This is the default screen shore...

Страница 53: ...ates 25 50 load capacity Appears in AC mode only and sometimes in Fault mode Indicates 0 25 load capacity Indicates AC mode in which shore power is available and passing through to the loads Indicates...

Страница 54: ...re version Figure 11 Display Panel Batt MODE AC MODE VAC VAC OUTPUT INPUT 888 888 LCD Screen Status LED light ESC button Power button Scroll button OK button To cycle through the various feature setti...

Страница 55: ...ing is OFF 4 Continue pressing the Scroll button to cycle through the settings until you reach the desired setting 5 Press the button to make the setting permanent or Press the button to exit To chang...

Страница 56: ...ress the button to make the setting permanent or Press the button to exit To change the LBCO Shutdown delay timer By default the operational mode is set to 300 seconds 1 Press and hold the button for...

Страница 57: ...be ON to operate this feature This setting allows the inverter to operate Battery mode when an ignition control wire is connected to the ACC input terminal and a valid ignition signal is constantly d...

Страница 58: ...digital equipment like desktop computers The transfer time is similar to a UPS in which it allows the transfer of shore power AC MODE to the loads from battery power Batt MODE within 10 milliseconds...

Страница 59: ...et to 50 Hz load appliances must also be rated to operate from 115 VAC 50 Hz power 4 Continue pressing the Scroll button to cycle through the settings until you reach the desired setting 5 Press the b...

Страница 60: ...n to factory default settings 4 Continue pressing the Scroll button to cycle through the settings until you reach the desired setting 5 Press the button to make the setting permanent or Press the butt...

Страница 61: ...verter operation When the Freedom X s inverter Power button is turned ON and the AC source is outside the operating range or is disconnected the transfer switch automatically switches to Battery Mode...

Страница 62: ...ely 50 watts and remains below this level After reaching the end of the countdown timer the inverter automatically shuts down To change the countdown timer see To change the power save timer setting o...

Страница 63: ...does not have to deliver the starting current for all the loads at once and will help prevent an overload shutdown Turning the Audible Alarm ON or OFF The Freedom X s audible alarm can be silenced See...

Страница 64: ...ss than 20 milliseconds default to switch to operating in inverter mode and start drawing power from the battery The operating mode indicator will change to Battery Mode and the green Status LED for B...

Страница 65: ...2 Low Voltage Alarm LBCO 0 5 volts A silent low battery warning shows fault code on the LCD screen Low Voltage Shutdown LBCO The buzzer sounds a single one second low battery alarm beep and the LCD sc...

Страница 66: ...current draw is within the inverter s limits The unit will shut down and indicate an overload shutdown Over temperature Conditions During inverter operation when the Freedom X s internal temperature...

Страница 67: ...is not displaying an error code check the following to make sure the present state of the installation allows proper operation Is the inverter located in a clean dry adequately ventilated place Are th...

Страница 68: ...wn is imminent depending on the setting see Operating Limits on page 51 Inverting Check battery status and recharge if necessary Check for proper DC cable sizing Check for loose connections and tighte...

Страница 69: ...obstruction and remove it Large debris which may enter through the fan grille may impede the fan blades from turning When removing debris do not insert your fingers inside the grille Remove power from...

Страница 70: ...tinually overloading the inverter and subjecting it to over temperature conditions Although provided with integral protection against overloads continual overloading can damage the circuitry Failure t...

Страница 71: ...rify the unit is connected to a 12V battery Check the voltage regulation of the external charging system if any Unit overload or AC output short circuit fault code Reduce the load Make sure the load d...

Страница 72: ...d neither of the green status LEDs for AC mode and Battery mode is illuminated AC shore power is not available or out of operating range and the inverter is OFF Check AC shore power Turn the inverter...

Страница 73: ...ing normally AC pass through current is high The fan turns on and off during inverter mode The inverter is running continuously at high power Do not be alarmed the unit is performing normally The fan...

Страница 74: ...under load for example compressors and pumps Of the capacitor start motors typical in drill presses band saws etc the largest you can expect to run is hp the transfer relays are rated at 2 hp Univers...

Страница 75: ...pecifications Freedom X Transfer relay rating 30A surge 24A continuous Transfer time shore to inverter Transfer time inverter to shore 20 millisecondsa a To change the AC Transfer time mode see To cha...

Страница 76: ...uency 60 or 50 Hzb b To set the AC Frequency see To change the AC Output Frequency on page 45 GFCI protection customer providedc c See Ground Fault Circuit Interrupters GFCIs on page 14 for approved d...

Страница 77: ...Freedom X Owners Guide book Page i Wednesday May 11 2016 10 32 AM...

Страница 78: ...Schneider Electric Solar Inverters USA Inc 1 800 670 0707 1 408 987 6030 http www xantrex com 975 0767 01 01 Printed in China Freedom X Owners Guide book Page ii Wednesday May 11 2016 10 32 AM...

Отзывы: