82
Freedom SW 230V Owner’s Guide
Troubleshooting
F86
Dead Battery Detected
Automatic
When battery voltage is
below the allowable
charging voltage.
Recharge the battery with an external
charging device.
If the error persists, then the battery may
be defective. Replace the battery.
F88
MPPT Ground Fault
Automatic
In a Xanbus network, an
MPPT has detected a
ground fault (MPPT
generated code
F56
).
Check the MPPT and correct the ground
fault.
Table 4
Fault Messages
Fault
Number
Message
Fault Type
Cause
Solution