975-0696-01-01
79
Troubleshooting
F57
FET1 Over Temperature
Automatic
Ambient temperature may
be too high.
Ensure adequate ventilation around the
Freedom SW.
Allow inverter to cool down and try
restarting.
Operating too large of a
load for too long while
inverting.
Remove excessive inverter loads.
Inverter cooling fan may
have failed.
If the temperature is above 40 °C, the fan
should be on. Hold your hand or a piece of
paper to the inverter vent to check if the
fan is working.
Both fans should be active at the same
time.
Inverter airflow intake may
be blocked.
Increase the clearance around the inverter
and/or unclog the airflow intake vents.
F58
FET2 Over Temperature
Automatic
Same as
F57
.
Same as
F57
.
F59
GOCFG process failed
Manual
The unit may be running
outdated firmware.
Clear the fault and check if the latest
firmware is installed. If not, download and
install the latest firmware from the
website.
Table 4
Fault Messages
Fault
Number
Message
Fault Type
Cause
Solution