STEP 3
Connect the wires to the appropriate terminals and implement the
protective bond wire connections called for above.
The Lightning Data Receiver is designed for use as a continuous real-time
threat indicator and controller that is connected and powered all the time.
NOTE
The relays in the Lightning Data Receiver may change state
momentarily when Receiver power is turned on and off, resulting
in undesirable or improper control functions. To prevent
improper lightning warning function and improper control
signaling, the Receiver should be powered continuously, except
for periods of routine maintenance.
The on-board batteries will reliably maintain relay states during failures of
commercial power (150 hours typical back up time for fresh alkaline
batteries).
Strike Guard Lightning Warning System
27
DEC 2013