Installation
System 182-XT-4
3 - 44
ba75753e06
12/2014
3.10.2 Usage of the auxiliary voltage
The DIQ/S 182 XT-4 has a 24 V output (designation,
HILFSSPANNUNG or AUXILIARY VOLTAGE on the terminal strip).
You can use this auxiliary voltage for the relay-controlled opening of the
valve in a DIQ/CHV valve module for the compressed air-driven sensor
cleaning function. To do so, you have to connect the auxiliary voltage
output, a free relay contact and the valve connection in the DIQ/CHV in
series. Bridge a terminal of the auxiliary voltage output with a terminal
of a relay output and run a control line from the remaining terminals to
the valve module.
NOTE
The auxiliary voltage must not be used for other purposes.
Connection scheme for one sensor with compressed air cleaning
NOTE
Run the bridge below the divider so the bridge does not bump against
the circuit board in the lid when the enclosure is closed.
17
Close the enclosure of the DIQ/S 182 XT-4.
X13
X15
X6
X12
X14
X5
X11
X4
X10
X3
X9
X2
X8
X1
Terminal strip
DIQ/S 182
Terminal strip
DIQ/CHV
R1
HILFS-
SPANNUNG
AUXILIARY
VOLTAGE
VENTIL
VALVE
VERTEILER
DISTRUBUTION
R2
R3
Valve
control line
Содержание DIQ/S 182-XT-4
Страница 6: ...Contents System 182 XT 4 0 4 ba75753e06 12 2014 ...
Страница 14: ...Safety System 182 XT 4 2 4 ba75753e06 12 2014 ...
Страница 68: ...Installation System 182 XT 4 3 54 ba75753e06 12 2014 ...
Страница 86: ...Operation System 182 XT 4 4 18 ba75753e06 12 2014 ...
Страница 92: ...The SETTINGS menu System 182 XT 4 5 6 ba75753e06 12 2014 ...
Страница 128: ...Maintenance and cleaning System 182 XT 4 7 2 ba75753e06 12 2014 ...
Страница 144: ...Technical data System 182 XT 4 9 12 ba75753e06 12 2014 ...
Страница 146: ...Accessories and options System 182 XT 4 10 2 ba75753e06 12 2014 ...
Страница 150: ...Appendix store separately if required System 182 XT 4 12 2 ba75753e06 12 2014 ...
Страница 151: ......