Rectifying faults
4.5
Faults that are not displayed
4.5.1
Appliance faults
Boiler indicates P1, P2, P3 at start-up and then restarts with P1..
Check
Action
1.
Fuse T 1.6 A (312) defective.
yes:
B
Turn ON the appliance.
B
Change the fuse.
B
Power OFF the appliance.
Start sequence not completed?
no:
↓
2.
The PCB control board is damaged.
B
Change PCB control board.
Excessive burner noise, rumbling noises
Check
Action
1.
Does the gas supply type match the
specifications on the appliance iden-
tification plate?
yes:
↓
no:
B
Convert appliance to correct gas type
1)
.
2.
B
Test gas supply pressure - OK?
yes:
↓
no:
B
Decommission appliance.
B
Notify gas company.
3.
Problem with flue?
B
Check CO
2
level in combustion
air.
> 0,2 % CO
2
?
yes:
B
Check flue and repair or replace if necessary.
no:
↓
4.
B
Remove silencer, flue pipe and
mixer unit.
Is internal flue pipe/silencer dirty or
clogged or are seals defective or
incorrectly fitted?
yes:
B
Repair or replace components.
B
Grease seal before fitting,
B
Make sure it is fitted in correct position.
no:
↓
5.
Flue gas CO
2
levels measured at
min. and max. load do not match
specified levels
.
B
Measure CO
2
levels.
yes:
B
Adjust CO
2
levels.
no:
B
Power OFF the appliance.
B
Change the gas valve.
B
Turn ON the appliance.
1)
See installation instructions