7 181 465 347 (01.07)
Rectifying faults
25
E 2
flashing.
The heating outlet NTC sensor is damaged.
Check
Action
1.
B
Activate menu option
Show service parameters
.
B
Select
.1 Flow temp.sensor
.
Is a temperature between
0.
and
5.
displayed?
yes:
The heating outlet NTC sensor is in short circuit:
B
Power OFF the appliance.
B
Replace CH flow NTC sensor; observe fitting
instructions for NTC sensor when doing so.
B
Turn ON the appliance.
E2?
no:
2.
Heating outlet NTC sensor:
Temperature between
95
. and
100.
is
displayed.
yes:
The CH flow NTC sensor is interrupted:
B
Power OFF the appliance.
B
Replace CH flow NTC sensor; observe fitting
instructions for NTC sensor when doing so.
B
Turn ON the appliance.
E2?
no:
↓
3.
Check if the 20-pin connector lead
assembly is damaged.
B
Power OFF the appliance.
B
Change the 20-pin connector lead assembly.
B
Turn ON the appliance.
E2?
4.
The PCB control board is damaged.
B
Power OFF the appliance.
B
Disconnect the boiler electrical connection.
B
Change PCB control board.
B
Reconnect the boiler electrical connection.
B
Turn ON the appliance.