6 720 610 597 GB (03.02)
Individual settings
33
7
Individual settings
7.1
Mechanical settings
7.1.1
Checking the size of the expansion vessel
System Capacity – BS7074:1
7.1.2
Setting the central heating flow tempera-
ture
The central heating flow temperature can be set to
between 35˚C and 88˚C.
Limited maximum setting for low-temperature
operation
The temperature control is factory limited to setting E,
giving a maximum flow temperature of 75˚C.
Adjustment of the heating output to the calculated heat
demand is not required by the heating systems regula-
tions.
Removing the maximum setting limit
For heating systems which require higher flow temper-
atures, the maximum setting limit can be removed.
B
Lift off the yellow button on the temperature control
with a screwdriver.
Fig. 39
B
Rotate yellow button through 180° and replace (dot
facing inwards).
The CH flow temperature is no longer limited.
7.2
Settings on the Bosch Heatronic
7.2.1
General description
The text display module provides a convenient means of
setting various appliance functions.
This description is limited to those functions necessary
for commissioning.
Displaying service functions
All service functions are displayed.
B
Press any button to activate the main menu.
B
Press
or
button until the arrow cursor is
pointing to Settings.
B
Press the
button.
B
Press
or
button until the arrow cursor is
pointing to Service.
B
Press the
button.
B
Press the
button to select Display service
parameters.
Service function 0.0, Last fault is displayed.
B
Press the
or
button to cycle through the
current settings.
B
Press the
button to exit the menu.
Expansion Vessel Pressure
and System Capacity
ZWBR
7-30
ZWBR
11-35
Expansion Vessel
litres
18
10
Expansion Vessel
Charge Pressure
bar
0.75
0.75
System
pressure
and
capacity
1 bar
litres
82
147
1.5 bar
litres
46
82
Table 11
i
With underfloor heating systems, observe
the maximum permissible flow tempera-
tures.
6 720 610 332-27.1O
Control setting
CH flow temperature
1
approx. 35˚C
2
approx. 43˚C
3
approx. 51˚C
4
approx. 59˚C
5
approx. 67˚C
E
approx. 75˚C
max
approx. 88˚C
Table 12
Service function
code no.
see
page
Anti-cycle time
2.4
34
Max. CH flow temp.
2.5
34
Max. heating output
5.0
34
Constant hot water cycle-
time
6.8
34
Variable pump settings
7.0
34
Table 13
i
For a detailed description, refer to Service
Booklet for the Engineer 7 181 465 347.