Rectifying faults
33
F 7
and
flashing.
Although appliance switches off, flame still detected
Check
Action
1.
Electrode(s) dirty or defective.
B
Power OFF the appliance.
B
Replace electrode assembly.
B
Turn ON the appliance.
B
Press
, does appliance restart???
F7?
2.
B
Power OFF the appliance.
B
Disconnect the boiler electrical
connection.
B
Remove PCB control board.
PCB control board damp?
yes:
B
Dry PCB control board (e.g. with hair dryer).
B
Refit PCB control board.
B
Reconnect the boiler electrical connection.
B
Press
, does appliance restart???
F7?
no:
↓
3.
Is there a problem with the flue?
B
Check CO
2
level in combustion
air.
> 0,2 % CO
2
?
yes:
B
Check flue and repair or replace if necessary.
no:
↓
4.
The PCB control board is damaged.
B
Power OFF the appliance.
B
Disconnect the boiler electrical connection.
B
Change PCB control board.
B
Reconnect the boiler electrical connection.
B
Turn ON the appliance.