INSTALLATION
Greenstar Ri Compact 6 720 646 610 (2013/12)
24
To reduce the flue length further:
Fig. 36 Further reduction
▶ Mark the length required for the terminal as shown (min.130mm) and
cut square, taking care not to damage the tubes.
▶ Remove any burrs and chamfer the edges of the tubes to assist ease
of connection and prevent seal damage.
▶ Push the terminal fully home into the turret and secure the terminal
end with the screws (3), ensure that the “TOP” label is facing up.
4.5.3 INSTALLING THE TELESCOPIC FLUE:
Refer to figure 37.
1. Set the flue length to the distance required, secure with screws
provided.
2. Seal the joint with the aluminium tape provided.
3. Slide the inner wall seal onto the terminal.
4. If fitting from inside the building; slide the outer wall seal onto the
terminal.
Fig. 37 Telescopic flue
Refer to figures 38 & 39.
1. Remove the three inner flue tube retaining screws (2).
The inner tube will be held in place in the appliance.
2. Check the boiler flue seal is correctly seated and apply silicone
grease.
3. Position terminal through the flue opening in the wall to the outside of
the building by the distance shown.
- or -
If the outer seal is already fitted, push the terminal through the hole
until the outer seal is outside and then pull the terminal back to the
wall to seal.
4. Align the flue turret to the boiler flue outlet with flat facing (1) to the
rear of the boiler.
The flue turret should be pushed straight down, on to the boiler.
Fig. 38 Aligning the turret
▶ Fit the screws removed in step 1 to secure flue turret.
▶ If fitting the outer seal from outside the building, slide the outer wall
seal onto the terminal as shown.
▶ “Make good” the gap between the flue and inner wall and if possible on
the outer wall.
Fig. 39 Telescopic flue installation
ADDITIONAL NOTES AND REMINDERS:
• Ensure that all cut lengths are square and free from burrs.
• The flue is sealed when assembled correctly and the components are
pushed fully home and secured by the screws provided.
• The flue is set at an angle of 3° or 52mm per metre length.
Fig. 40 Slope for condensate disposal
4.5.4
FLUE TERMINAL PLUME RE-DIRECTION:
The flue discharge can be re-directed allowing some plume redirection
control, alternatively, a complete plume management system can be
fitted to the flue terminal.
RE-DIRECTING THE FLUE DISCHARGE
1. Unclip (1 & 2) the terminal end and rotate through 180°.
The aluminium tape is not required when reducing the
terminal.
The turret securing screws are from the boiler and are
not in flue kit.
4
5
6
1
130 mm
265 mm
MIN
6720643895-32.2Wo
3.
4.
1.
1.
2.
TOP
6720644842-08.1Wo
For more information refer to the 60/100 Horizontal
Flue kit Instruction Manual
NOTICE:
DO NOT rotate the complete terminal
assembly.
6720646610-30.1W
o
1
2
1.
1.
1.
2.
6720643895-33.1Wo
3.
4.
110
6720644842-10.1Wo
2m
1m
52mm
104mm