INSTALLATION
Greenstar Ri Compact 6 720 646 610 (2013/12)
23
▶ When the condensate connections are complete, pour approximately
200 to 250ml of clean water through the inner flue opening on top of
the boiler to fill the siphon.
Fig. 32 Pipe work dimensions
4.5
FLUE INSTALLATION
HORIZONTAL FLUE (60/100mm diameter)
For vertical flues and 80/125mm horizontal flues, please refer to
separate instructions supplied with the flue kit.
Basic instructions for the 60/100mm diameter flue are shown below.
Fig. 33 Flue turret centre
4.5.1
MEASURING THE FLUE (STANDARD FLUE):
▶ Measure from the outside of the wall to the centre line of the flue turret
to determine length L.
▶ Subtract 50mm from the length L to give the correct dimension to the
flue elbow connection.
▶ If the length L falls within the telescopic range of 350 to 570mm or
570 to 790mm using the longer telescopic flue, then no cutting will be
required.
▶ If the required length is less than 350mm the standard telescopic flue
can be modified, refer to fig. 35.
▶ If the required length is greater than 570mm, then the longer
telescopic flue, giving a range of 570 - 790mm, can be used
▶ If the required length is greater than 790mm, then flue extensions will
have to be used. Refer to the 60/100 Horizontal Flue Instruction
manual provided in the telescopic flue kit.
▶ Refer to section 3.7 for flue options.
Adjusting the telescopic flue length:
Fig. 34 Standard telescopic flue
Extend tube (1) by withdrawing from tube (2) to achieve the flue length
required, between 350 - 570mm or 570 to 790mm if using the longer
telescopic flue.
Secure with screw provided and seal joint with the aluminium tape
supplied.
4.5.2
REDUCING THE TELESCOPIC FLUE LENGTH
The flue terminal MUST be fitted with the 'TOP' label uppermost to allow
the correct fit and use of the plume management system.
Fig. 35 Reducing the standard terminal
▶ Remove securing screws (3) to detach the terminal assembly from the
turret.
▶ Slide terminal section (2) from the terminal assembly and discard.
▶ To use terminal (1) without cutting remove the location lug (4) on the
inner flue tube (5) and remove any burrs.
▶ Push the terminal fully home into the turret and secure the terminal
end with the screws (3).
To ease assembly of flue components, apply silicone
lubricant to sealing surfaces.
6720646610-09.1W
o
WALL
23mm
149mm
23mm
6720646610-29.2W
o
170 mm
Edge
of
case
WALL
195 mm
Ensure that the “TOP” label is facing up before securing
the flue section to the turret.
6720643895-30.1Wo
570 mm
350 mm
L
2
1
6720643895-31.1Wo
2
3
1