Manual 26727
VariStroke-I (VS-I) Electro-hydraulic Actuator
Woodward
49
Demand Analog Inputs
There are two demand analog inputs to the VS-I. Demand Input #1 is dedicated to the demand input. For
application where reliability is critical, the Demand Input #2 can be configured for a redundant demand
input.
Figure 3-12. Analog Input Connections
Calibrated Accuracy: 0.1% of full range
Input Range: (0 to 25) mA, the recommended maximum range is (2 to 22) mA
Maximum Temperature Drift: 200 ppm/°C
Input Impedance: 200
Ω
±10%
Common Mode Voltage Range: ±50 V(dc)
Common Mode Rejection Ratio: 70 db @ 50 Hz & 60 Hz
Isolation: 400 k
Ω
from each terminal to circuit common, 500 V(ac) to chassis ground
Analog Input Wiring Requirements:
•
Individually shielded twisted pair cable
•
Keep this and all other low level signal cables separated from input power cables to avoid
unnecessary coupling (noise) between them.
•
Wire Gauge Range: (0.14 to 1.5) mm
²
/ (16 to 24) AWG
•
Shielding: per drawing above