Manual 37187A
SYNCONpanel - Transportable Remote Synchronizing Panel
SYNCONpanel
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The SYNCONpanel consists of the SYNCON unit described under SYNCON Unit on page 14 and various con-
trol switches and buttons as well as measuring inputs.
11
12
13
14
15
16
17
18
19
Figure 5-2: SYNCONpanel front
Push Buttons
The following push buttons are utilized to remote control the synchronization process on the SYNCONpanel.
11
EMERGENCY STOP
Emergency Stop
The emergency stop button generates an alarm in the GCP that opens
the GCB and stops the engine immediately.
Note:
For safety reasons, it is absolutely necessary that the connec-
tion with the GCP and the configuration of the GCP's discrete
input are correct.
12
Start Synch
Start synchronization
This push button starts the synchronization sequence with phase
matching. If the two systems are synchronous, the lamp in the push
button illuminates.
13
Unload mains
Unload mains
This push button initiates the mains unloading sequence. The load
will be ramped from the mains to the generator.
Note:
The unload mains push button can only be used if the SYN-
CONpanel is measuring the current.
14
Unload generator
Unload generator
This button initiates the generator unloading sequence. The generator
performs the unloading function and opens the GCB.
Page 18/27
© Woodward