Manual 37187A
SYNCONpanel - Transportable Remote Synchronizing Panel
Chapter 4.
Mobile System Modes
The operating modes of the Rental Package GCP-31/
RPQ
+
SC08
are usually selected via an external selector
switch and the digital inputs. A typical connection of the selector switch and a description of the operating modes
belonging to it may be found in the following.
OFF
Isolated
operation
Transfer
operation
Peak load operation
internal
Peak load operation
external
Emergency oper.
Start
For this, the signals are to be connected as follows:
Signals to be con-
nected
Operating mode
Terminal 54
Reply MCB
OFF
Terminal 126
Mobile Sys-
tems
Terminal 53
Enable MCB
Terminal 68
Inhibit emer-
gency run **
Terminal 3
Automatic 1
Terminal 5
Automatic 2
OFF (de-energized)
irrelevant
irrelevant
irrelevant irrelevant
irrelevant irrelevant
Isolated operation
1
0
0
1
remote control
0
Transfer operation
1
1
0 (Syncon Pa-
nel)
remote control
*
1 remote
control
irrelevant
Peak load operation
internal
0 0 1 1
remote
control
0
Peak load operation
external
0 0 1 1
0 remote
con-
trol
Emergency opera-
tion
Start
reply must be
connected
0 1 0
0 0
*)
If a synchronization between mains and generator busbar voltage is to be performed without SYNCON Panel, this DI
must initiate the synchronization.
**) If no emergency power operation is required, the parameter "Emergency run" may be disabled. This allows to use termi-
nal 68 as free alarm input.
Page 10/27
© Woodward