SYNCONpanel - Transportable Remote Synchronizing Panel
Switch Position Emergency Power Start
The GCP operating modes are enabled:
STOP:
Genset stops with cool down or remains stopped. If necessary, the load will be taken off of the
genset and the GCB will be opened.
MANUAL:
Genset may be started and stopped manually.
The generator breaker may be closed and opened using the manual keys.
No automatic change-over to emergency power is activated.
AUTOMATIC:
If mains fail (measurement via terminals 50, 51, 52) the genset will be started, the MCB will be
opened and the GCB will be closed. If mains return, the MCB will be synchronized back after
the mains settling time has expired. Then the load will be taken off of the genset and the genset
will be stopped.
TEST:
The genset will be started. The generator breaker may be closed and opened using the manual
keys. An automatic change-over to emergency power will be performed if necessary.
The set points for frequency and voltage may either be modified using the arrow keys at the unit or via the digital
inputs.
NOTE
It is required for the emergency power start function that the MCB reply is connected. The start and
stop commands from the GCP must also be wired to the MCB to enable an automatic change-over.