Manual 37187A
SYNCONpanel - Transportable Remote Synchronizing Panel
Appendix A.
Technical Data
Measuring
values, voltages ----------------------------------------------------------------------------------
Busbar measuring input: front / back switchable
Mains measuring input: front
Front measuring inputs with internal fuse 5x20 mm 5 A slow-to-blow
Rated measuring voltage (V
rated
) ................................................................................230 Vac
Accuracy ......................................................................................................................Class 1
Linear measuring range ..........................................................................................1.3 × V
rated
Maximum power consumption per path .................................................................. < 0.15 W
Input resistance ..............................................................................................approx. 0.7 M
Ω
Measuring values, current -------------- via clamp-on transducer (1mV/1A ac or 10mV/1A ac)
Voltage signal measuring input for current measurement: front
Rated measuring voltage (V
measI
) ...................................................................................1 Vac
Accuracy ......................................................................................................................Class 1
Linear measuring range ..............................................................................................1.6 Vac
Input resistance ............................................................................................approx. 0.21 M
Ω
Measuring
values, frequency --------------------------------------------------------------------------------
Rated measuring frequency (f
N
)................................................... 50/60 Hz (40.0 to 70.0 Hz)
Ambient
variables ---------------------------------------------------------------------------------------------
Power supply (V
aux
) ............................................................................ 24 Vdc (18 to 32 Vdc)
Intrinsic consumption ............................................................................................max. 12 W
Ambient temperature ...........................................................................................-20 to 70 °C
Ambient humidity .................................................................................95 %, not condensing
Emergency Stop output----------------------------------------------------------------------potential free
Contact type ........................................................................................... N.O. (make-contact)
Switching voltage ........................................................................................ max. 250 Vac/dc
Interface -----------------------------------------------------------------------------------------------isolated
Insulation voltage....................................................................................................3,000 Vdc
Version..........................................................................................................CAN bus (CAL)
Housing ----------------------------------------------------------------------- portable with hinged cover
Type .....................................................................................................Peli 1300 Case Plastic
Dimensions (W × H × D)............................................approx. 270 mm x 174 mm x 246 mm
Front connector ................................................................ safety connectors 4 mm² (isolated)
Back connector ........................................................................ Industrial connector, A series
(Harting HAN-A, Type 0920 010 2612)
Weight.............................................................................................................. approx. 3.3 kg
Protection -------------------------------------------------------------------------------------------------------
Protection system ............................................................................................................IP 65
with closed cover and proper installation
Protection system ............................................................................................................IP 40
with open cover and proper installation
EMV test (CE) ................................................. tested according to applicable EN guidelines