Parameter setup report
Wolf recommends you complete the setting report carefully and to keep it safe to enable a quick
solution to be found during service and in case of a full reset.
Parameter
Setting range
Factory
setting
Individual
setting
A09
Frost protection level
-20 to +10 °C
+2 °C
A10
Parallel DHW operation
0 / 1
0
a14
Maximum DHW temperature
60 to 80 °C
65 °C
HG01
Burner switching differential
(dynamic)
5 to 30 K
15 K
HG06
Pump operating mode
0 / 1 / 2
0
HG07
Run-on time
Boiler circuit pump
0 to 30 min
3 min
HG08
Maximum limit
Boiler circuit TV-max
40 to 90 °C
75 °C
HG09
Burner cycle block
1 to 30 min
4 min
HG13
Programmable Input E1
1 to 11
1
HG14
Programmable Output A1
0 to 14
0
HG15
Cylinder hysteresis
1 to 30K
5 K
HG19
Run-on time
Cylinder primary pump
0 to 10 min
3 min
HG20
Max. cylinder heating time
0 to 5 h
2 h
HG21
Minimum boiler water *
temperature TK-min.
38 to 90 °C
38 °C
HG22
Maximum boiler water temperature
TK-max.
50 to 90 °C
80 °C
HG24
DHW sensor operating mode
1 / 2 / 3
1
HG25
Excess boiler temperature during
cylinder heating
0 to 40 K
10 K
HG26
Boiler soft start
0 / 1
1
HG32
Return temperature raising **
0 to 70 °C
30 °C
HG33
Hysteresis time
1 to 30 min
10 min
HG34
eBUS feed
0 / 1 / 2
2
HG35
0 - 5 V input for telecontrol system
0 / 1
0
HG50
Test functions
1 to 5
-
HG70
Display
Multi function
input E1
-50 sensor short circuit or contact closed
-60 sensor lead break or contact open
Actual temperature header sensor HG13 = 7
Actual temperature return sensor HG13 = 11
* set to 50 °C for pressure jet gas burners
** set to 40 °C for pressure jet gas burners