15
3061809_1210
Pump operating mode 2:
Buffer primary pump for BSP cylinder
The header sensor (buffer) only affects the heating operation. In
case of cylinder heating, the reference temperature is provided
by the internal boiler sensor. In heating mode, the buffer primary
pump runs only when there is a burner demand. Pump run-on in
accordance with parameter HG07.
Soft starting: At TK
Ist
< TK
min
(38 °C) buffer primary pump and
cylinder primary pump "OFF". MKP continues to run with soft
starting.
Note: Increase the pump run-on time from 3 min to 15 min.
Set the parameter HG13 to 7.
ZUP = Feed pump
SPLP = Cylinder primary pump
PLP = Buffer primary pump
SF = Cylinder sensor
SAF = Header sensor
MK1 = Mixer circuit
MKP = Mixer circuit pump
MKP
MK1
Wood
boiler
Buffer cylinder
Oil/gas boiler
SAF
SF
PLP
SPLP
Solar thermal system
integration
Hydraulic scheme:
Contractor level parameters