Contractor level parameters
The cylinder hysteresis regulates the start and stop points for
cylinder heating. The higher the ON / OFF temperature differential,
the higher the cylinder temperature fl uctuation around the set
cylinder temperature.
Example: Set cylinder temperature 60 °C
Cylinder hysteresis 5 K
Cylinder heating commences at 55 °C and ends at 60 °C.
Cylinder hysteresis
Parameter HG15
HG15
5
Factory setting: 5 K
Setting range: 1 to 30 K
Individual setting: ______
No. Explanation
12
Bypass pump for return temperature raising
Output A1 is controlled if the return temperature is lower
than the selected return temperature raising value
(parameter HG32).
Important: Input E1 must, in any case, be
programmed to setting 11 or if an external
burner block input E1
(HG13 = 8) has been programmed.
13
DHW circulation pump
Output A1 is controlled for 5 minutes after a pushbutton has
been activated (pulse input E1).
Important: In any case, input E1 must be
programmed to setting 6.
14
Output A1 ON
Output A1 is controlled if input E1 is closed
(external burner demand).
Important: In any case, input E1 must be
programmed to setting 10.