Contractor level parameters
Each time the burner is shut down in heating mode, it will be
blocked for the duration of the burner cycle block.
The burner cycle block is reset by switching the ON / OFF switch
OFF and ON or by briefl y pressing the reset button.
Individual setting: ______
Burner cycle block
Parameter HG09
HG09
4
Factory setting: 4 min
Setting range: 1 to 30 min
This function limits the boiler water temperature upwards in heating
mode, and the burner shuts down. This parameter has no function
during cylinder heating, and the boiler water temperature may also
be higher during this time. "Re-heating effects" can result in the
temperature being exceeded a little.
Individual setting: ______
Maximum limit
Boiler circuit TV-max.
Parameter HG08
HG08
75
Factory setting: 75 °C
Setting range: 30 to 90 °C
Subject to there being no heat demand from the heating circuits,
the boiler circuit pump will run-on in accordance with the set time,
to prevent a boiler safety shutdown at high temperatures.
Individual setting: ______
Run-on time
Boiler circuit pump
Parameter HG07
HG07
3
Factory setting: 3 min
Setting range: 0 to 30 min
Programmable input E1
Parameter HG13
HG13
1
Factory setting: 1
Setting range: 1 to 11
The functions of input E1 can only be scanned and adjusted with
Wolf control accessories with eBUS capability.
The following functions can be allocated to input E1:
No.
Explanation
1
Room thermostat
With open input E1, heating operation will be blocked
(summer mode), independent of any digital Wolf
control accessories.
Exception: Remote controlled heating circuits