Contractor level parameters
No. Explanation
2
Maximum thermostat
To enable the burner, input E1 must be closed. The
burner will remain blocked for as long as the contact is
open, even in emissions test mode, cascade mode and
for DHW and central heating frost protection mode.
3
N / A
4
N / A
5
Flue gas damper / ventilation air damper
Function monitoring of the fl ue gas damper/
ventilation air damper with fl oating contact. Closed
contact Condition for burner enable in central
heating, DHW, cascade and emissions test mode.
Important: A1 (HG 14 = 7) must be programmed for
fl ue gas damper / ventilation air damper
function.
6
DHW circulation push button (on site)
After activating this button, the DHW circulation pump
is operated for 5 minutes, independent of
the time program or the position of the program
selector (BM).
Important: In any case, output A1 must be
programmed to setting 13.