STÖRUNGSANALYSE:

 

 

 

TROUBLE SHOOTING:

 

 

Nr. 

 

Erscheinung 

 

Ursachen und Behebung

 

 

No. 

 

Symptom 

 

Possible Causes

 

 

 

Schwimmerkugel im ECO 
öffnet nicht im Automatikbe-
trieb 

-

  Zu klein dimensionierter Regler? 

-

  Eintritts-/Austrittventil verschlossen? 

-

  Nicht ausreichend Gas vom Verdichter abgesaugt (Einstel-

lung Differenzdrukregler oder Verdampferdruckregler 
überprüfen) 

-

  Schieberersteuerung z.B. durch Ablagerung oder Korrosi-

on blockiert 

-

  Schwimmerkugel defekt 

 

Regulator does not open 
during automatic operation 
 

Too small selected regulator? 

Closed inlet-/outlet valve? 

Too high pressure difference? 

Low-pressure nozzle too small or blocked? 

Moisture in the system, now pressure nozzle is frozen? 

Slide regulation is blocked, e.g. with debris or due to 

corrosion 

Float ball is damaged 

 

 

Regler schließt nicht 

-  falsche Schwimmerkugel (ggf. austauschen) 
-  Transportsicherung des Hebels (Loch im Hebel muss nach 

unten weisen) 

-  Schiebersteuerung verschlissen (ggf. austauschen) 
-  Störung des Differenzdruckregler  

 

Regulator does not close 

False float ball (can be exchanged) 

Transport safety device blocks the float ball (lever respec-

tive hole in the lever shall face down) 

Slide block is worn (can be exchanged) 

Opening of the low pressure nozzle is too big (or: when 

connecting a solenoid valve line the low pressure nozzle 
is not closed) 

 

 

NGX spricht an (ECO über-
füllt) 

-  Unzureichender Differenzdruck zur ND-Seite 

-  Funktion des Differenzdruckreglers prüfen 
-  Verdampferdruckregler zu niedrig eingestellt 
-  Zu großer Druckverlust in der Einspritzleitung hinter dem 

ECO (zu große Steigung, zu viele Widerstände) 

-   

 

NGX is activated (ECO over 

filled) 

Differential pressure to the LP side not sufficient 

Check function of the differential pressure regulator 

Evaporation pressure regulator set too low 

Pressure losses in thelow pressure line from the ECO too 

high (e.g. too steep slope) 

 

Zu hoher Verflüssigungdruck 
durch Rückstau 

-  Siehe HR-Betriebsanleitung 
-  Verdampferdruckrtegler zu hoch eingestellt 
 

 

Too high condensing pressure 
because of back-up 

 

See high side float regulator instructions 

Evaporation pressure regulator set too high 

 

 

Stark schwankender Druck 

auf der ND-Seite 

-  zu geringe Kältemittelfüllung 
-  hohe Reibkräfte an der Schiebersteuerung (Innenteile auf 

Ablagerungen bzw. Korrosion prüfen) 

-  Regler wurde überdimensioniert 

 

Heavy fluctuating pressure on 
the LP side 
 

Too low refrigerant charge 

High friction at the slide block (look for any debris or 

corrosion) 

Float regulator is too big 

 

 

Minimalstandalarm auf der 
Niederdruckseite 

-  siehe Pkt. 4 
-  Verflüssiger im Winter mit Kältemittel gefüllt (einzelne oder 

alle Verflüssiger absperren) 

-  Zu geringe Kältemittelfüllung 

 

Minimum level alarm on the LP 
side 
 

 See point 4 

Condenser is backed up with refrigerant (isolate one or 

more condensers) 

Too low refrigerant charge 

7

 

Verdichter schaltet ab

 

-  Motor wegen zu hohem ECO-Druck überlastet 

-  Verdampferduckregler einsetzen 
-  Einstellung Verdampferdruckregler prüfen 

7

 

Compressor is switched off 

Motor overloaded due to high ECO pressure 

Suction pressure regulator fittet? 

Check setting of suction pressure regulator 

Содержание ECO 2-L

Страница 1: ...1 ECONOMIZER ECO Montage und Betriebsanleitung Installation and operating instructions...

Страница 2: ...NG 16 11 4 AUSTAUSCH DER VENTILPACKUNG 16 12 FEHLERSUCHE 16 1 INTRODUCTION 3 1 1 INTENDED USE 3 1 2 SAFETY REQUIREMENTS 3 1 3 MANUFACTURER DISCLAIMER 3 2 TERMS OF WARRENTY 4 3 TECHNICAL INFORMATION 4...

Страница 3: ...en Fall berschritten werden Under no circumstances are the stated design temperature and pressure limitations on the data plate to be exceeded Wenn am Eintritts und am Austrittsstutzen Absperr ventile...

Страница 4: ...ted are not used or disconnected There have been modifications made to the high pres sure float regulator without the manufacturers written approval The safety regulations are not adhered to The econo...

Страница 5: ...h pressure float regulator with valves WITT stop valves fitted to inlet and outlet connec tions gor gas and liquid refrigerant Drainage valve EA 10 GB L Purge valve EE6 L from 1 1 2007 before EA10 GB...

Страница 6: ...r ECO housing ECO 2 and 3 Max allow Pressure PS 25 bar between 50 10 C Max allow Pressure PS 18 75 bar between 10 60 C Test pressure Pt 36 bar ECO 4 Max allow Pressure PS 22 bar between 50 10 C Max al...

Страница 7: ...1370 610 700 725 575 335 355 1460 208 ECO3 HR2 600 395 200 880 559 60 3x2 9 88 9x3 2 42 4x2 6 800 1460 650 750 850 725 460 480 1750 298 ECO3 HR3 600 395 200 880 559 60 3x2 9 88 9x3 2 60 3x2 9 800 1460...

Страница 8: ...8 4 4 Abmessungen Fig 2h 4 4 Dimensions ECO 4 HR 4...

Страница 9: ...sing This is returned directly to the compressor suction line via a top mounted connection Durch die Drosselgasabsaugung werden sowohl die Verdichter als auch die Abscheider entlastet und diese k nnen...

Страница 10: ...essure regu lator 1 is required Anlage mit Verdampferdruckregler auf der Saugseite Fig 4 Installation with evaporation pressure regulator Wenn der Verdichter gegen zu hohen ECO Druck ge sch tzt werden...

Страница 11: ...e intermediate temperature tm sufficient refrigerant gas has to be drawn off the ECO top suction connection Whereby the intermediate pressure is depending on the screw compressor manufacturer s design...

Страница 12: ...city you will ensure that flash gas is kept to a minimum Auf keinen Fall darf die Zulaufleitung unisoliert durch warme R ume gef hrt werden oder ne ben warmen Maschinen montiert sein noch direkter Son...

Страница 13: ...s Transports ist Hebelstellung im Anlieferzustand so dass die Bohrung im Hebel nach oben gerichtet ist Transport sicherung For safe transportation during delivery the float ball is locked in position...

Страница 14: ...HR2 sind an den Schwimmer bzw ECO Geh usen Nocken f r Sicherheitsventile vorgesehen Above size HR 2 the float regulator respective ECO hous ing is equipped with a safety valve connection Drehen Sie d...

Страница 15: ...REPLACING THE FLOAT BALL Beachten Sie beim Ausbau unbedingt die lokalen Unfall Verh tungs Vorschriften Beachten Sie insbesondere folgendes Pr fen Sie Fluchtm glichkeiten um im Notfall schnell die Gefa...

Страница 16: ...12 TROUBLE SHOOTING Trotz des einfachen mechanischen Prinzips der Hoch druckschwimmer Regelung kommt es bei ausgef hrten Anlagen gelegentlich zu Problemen Erfahrungen haben gezeigt dass in den meisten...

Страница 17: ...gler zu niedrig eingestellt Zu gro er Druckverlust in der Einspritzleitung hinter dem ECO zu gro e Steigung zu viele Widerst nde 3 NGX is activated ECO over filled Differential pressure to the LP side...

Страница 18: ...18...

Отзывы: