8
1.
Important Information for System Operators
1.6 Functional test
EN 12828 and
ÖNORM B8131 require that the function of the system and related safety equipment be checked
and certified yearly by a qualified technician (installer, heating system contractor).
The heating water condition must be checked (ÖNORM H 5195) by a heating expert (installer) (see BioWIN assem-
bly instructions – heating water) at two-year intervals; this is to prevent corrosion and sediment accumulation in
the heating system and boiler. For systems using more than 1,500 litres of water (e.g., systems with accumulator
tanks), this inspection is required on an annual basis.
In the event of repair work requiring a change of water in the heating system, the heating water is to be checked
within 4 to 6 weeks after the repair work.
Corrosion and sediment resulting from incorrectly treated heating water are not covered by the guarantee and
warranty.
1.7 Filling the pellet store
Attention!
The pellet flue-connected stove must be turned off
correctly
at least 15 minutes before the store is
filled – Fig. 2.
Press the ON/OFF button. Never turn off using the emergency OFF switch!
Pressing any button will turn on the display. The boiler is only turned off when the ON/OFF button is pressed
after the display is turned on. Wait until burnout mode has finished (this will not be indicated on the display) and
open the combustion chamber doors.
During filling, negative pressure is created in the pellet store, which can cause burn-back in the pellet boiler.
Therefore, the boiler must be prevented from operating during the filling procedure.
Tip!
To prevent negative pressure arising in the pellet boiler, open the combustion chamber door (see
Fig. 3 and also section 2.2) and leave open during the filling process.
Every time the store is filled, the date and volume should be added to the “Storage room fill“ sticker – Fig. 4.
Fig. 2
Turning off boiler
Fig. 3
Opening combustion chamber
door during the filling process
002357/00
01/2010
Befüllung Lagerraum
Filling date and volume
Remplissage du silo de stockage
Datum/Date/Date
Menge/Volume/Quantité
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
kg
Fig. 4
“Storage room fill“ sticker on the
storage room door