background image

PSS60/E  

PSS90/E

GENERATOR

INSTALLATION AND 

OPERATORS MANUAL

COPY YOUR MODEL AND SERIAL NUMBER HERE

No other WINCO generator has the same serial number as yours. 

If you should ever need to contact us on this unit, it will help us to 

respond to your needs faster.

MODEL __________________________________________________

SERIAL NUMBER _________________________________________ 

PURCHASE DATE _________________________________________

DEALER NAME ___________________________________________

DEALER PHONE # ________________________________________

www.wincogen.com

16200-016

Содержание PSS60-17

Страница 1: ...d to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE D...

Страница 2: ...FUEL PRESSURE TABLES NG LP FUEL CONVERSION INSTALLING THE BATTERY 9 SERVICING BATTERIES BATTERY CHARGING CONNECTING THE BATTERY CHARGER BLOCK HEATER AC ELECTRICAL CONNECTIONS 11 DC ELECTRICAL INTERCON...

Страница 3: ...that you carefully read and follow the operating instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in...

Страница 4: ...h 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not s...

Страница 5: ...Ohms Per Ph 20 C Exciter Stator L L 20 00 Ohms 20 C Aux Winding 2 6 Ohms 20 C Voltage Regulator L L AS440 PSS90 E LP Gas Wattage 80 000 80 000 80 000 80 000 Volts 120 240 120 208 120 240 277 480 kvA...

Страница 6: ...tes at 1800 rpm and frequency regulation is maintained by the electronic governor within 5 cycles variation from no load to rated load The generator is a single bearing direct drive rotating field des...

Страница 7: ...t recommended for the PSS60 DO NOT use street ells restrictive INSTALLATION WARNING Before proceeding with installation be sure the operation selector switch is in the stop position and the battery di...

Страница 8: ...lve and has a drop tube inside the tank that is pulling fuel from the bottom of the supply tank Before starting the unit you must confirm that you have a good liquid supply at the unit Engine generato...

Страница 9: ...de of oil as recommended by the engine manufacturer s maintenance instructions The necessity of using the correct oil and keeping the crankcase full cannot be over emphasized Failure to do so will cau...

Страница 10: ...e generator assembly All connections must be clean and tight Check the electrolyte fluid in the battery periodically to be sure it is above the plates Never allow the battery to remain in a discharge...

Страница 11: ...e maximum load current without excessive voltage drop By code the wire must be heavy enough to handle the full current rating of the mainline circuit breaker or fuse in the entrance or sub panel prote...

Страница 12: ...ring of the Automatic Transfer Switch Because of the many different types of service feeder and distribution equipment no specific wiring instructions can be provided It is recommended that only coppe...

Страница 13: ...comes to a standstill Should a remote start signal be present while operating in this mode a remote start WILL NOT occur MANUAL MODE This button places the module into its Manual Mode Once in Manual...

Страница 14: ...cy on the digital display The voltage should be 208 240 480 AC depending on which model you have and a frequency of 59 5 to 60 5 hertz Hz If you have the proper voltage at the generator the next step...

Страница 15: ...NG When performing any type of maintenance on this equipment make sure the selector switch on the engine generator is in the off position If you are working in the Automatic Transfer Switch confirm wi...

Страница 16: ...st hold 12 Volts during cranking 2 Blown fuse on generator control panel 3 Loose or dirty battery terminals 4 Defective engine control module 5 Defective starter 6 Defective start solenoid 7 Locked up...

Страница 17: ...HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC WIRING...

Страница 18: ...B ENGINE HARNESS SCHEMATIC 6 1 6 1 1 3 6 237 21 2 22 17 6 1625 3 8 3 8 1 1 8 8 62 12 6 67 57 200 1 8 6 7 1 7 21 1 2 1 5 9 51 3 5 0 0 7 6 5 1 217 16 35235 7 5 1 250 7 21 21 1 72 1 2 81 87 25 86 6 352...

Страница 19: ...1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7 50 1 2 803 5...

Страница 20: ...omponent of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EX...