Product description
en
Installation and operating instructions Wilo NL-HE
11
Permissible ambient temperature
[t]
+104 °F
Permissible operating pressure
[P
max
]
232 psi
Flanges
125# ANSI in accordance with ASME B16.1
Permissible fluids
– Heating water
– Cooling/cold water
– Water-glycol mixture up to 40 % vol.
Protection class
IP21, IP23, IP55
Insulation class [Cl.]
F
Motor protection
See manufacturer’s documentation
Special version or with auxiliary equipment (at additional charge)
Permissible fluids
– Heating water
– Water-glycol mixture up to 40 % vol.
Special voltages/frequencies
Pumps with motors with different voltages or other
frequencies are available on request
Additional information CH
Approved fluids for heating pumps
– No oxygen binding agents, no chemical sealant.
– Ensure enclosed system from corrosion perspect-
ive.
Statement of date of manufacture
The date of manufacture is stated in the format: MMDDYYYY
ƒ
MM = month
ƒ
DD = day
ƒ
YYYY = year
4.4
Type key
Example: NL-HE 2x1.25x5-5-182/4T-460-2-TEFC
NL-HE
Product family
2
Nominal diameter of Suction Flange
1.25
Nominal diameter of Discharge Flange
5
Nominal diameter of the impeller in inches
5
Rated motor power in hp
182/4T
Motor Frame size
460
Motor rated voltage
2
Motor poles
TEFC
Motor Enclosure
4.5
Scope of delivery
Complete unit
ƒ
NL-HE pump
ƒ
Baseplate
ƒ
Coupling and coupling guard
ƒ
With or without electric motor
ƒ
Installation and operating instructions
Pump by itself:
ƒ
NL-HE pump
ƒ
Bearing bracket without baseplate
ƒ
Installation and operating instructions
Содержание NL-HE Series
Страница 1: ...Pioneering for You Wilo NL HE 3327453 Ed 01 2021 01 en Installation and operating instructions ...
Страница 2: ......
Страница 42: ......
Страница 43: ......