49
Connection terminal assignment
- Remove the screws and take off the
converter cover.
NOTICE: Terminals IN1, IN2, GND and Ext. Off meet
the requirements for “safe isolation” (in acc. with
EN 6180051) at the mains terminals as well as at
SBM and SSM terminals (and vice versa).
Type key
Assignment
Remarks
L1, L2, L3
Mains connection voltage
Threephase current 3 ~ IEC38
PE
Earth terminal
IN1
Sensor input
Signal nature: voltage (010
V, 210 V)
Input resistor: Ri ≥ 10 kΩ
Signal nature: current (020 mA, 420 mA)
Input resistor: R
b
= 500 Ω
Can be configured in the “Service” menu <5.3.0.0>
IN2
External setpoint input
Signal nature: voltage (010
V, 210
V)
Input resistor: Ri ≥ 10 kΩ
Signal nature: current (020 mA, 420 mA)
Input resistor: Rb = 500 Ω
Can be configured in the “Service” menu <5.4.0.0>
GND (x2)
Ground terminals
For each IN1 and IN2 input
+24 V
Continuous power supply for sensor
Max. current: 60 mA.
The power supply is protected from shortcircuits.
Ext. Off
ON/OFF control input
“DEACTIVATION priority”
for a potentialfree external switch
The potentialfree external switch is used to activate
and deactivate the pump.
On installations with high numbers of starts
(> 20 per day), activation and deactivations should
be performed via “Ext. Off”.
SBM
“Available transfer” relay
In normal operation, the relay is activated when the
pump is running or in standby.
The relay is deactivated if an initial malfunction occurs
or if the main power supply is disconnected (pump
switches off).
Pump availability, even temporarily, can thus be signalled to
the switchgear.
Can be configured in the “Service” menu <5.7.6.0>
Potentialfree contact:
minimum: 12 V DC, 10 mA
maximum: 250 V AC, 1 A
SSM
“Failures transfer” relay
If consecutive malfunctions of the same type are
detected (from 1 to 6 according to significance),
the pump switches off, and this relay is activated
(until manual intervention).
Potentialfree contact:
minimum: 12 V DC, 10 mA
maximum: 250 V AC, 1 A
PLR
Connection terminals of the PLR
communication interface
The optional IF module PLR can be inserted into the
multiple connector placed in the converter connector area.
The module is protected from polarity reversal.
LON
Connection terminals of the LON
communication interface
The optional IF module LON can be inserted into the
multiple connector placed in the converter connector area.
The module is protected from polarity reversal.
0.550.75
1.1 1.5
2.2
3 4 5.5
7.5
11 15 18.5
22
x1
x2
Installation and operating instructions – HELIXVE 223652
English
Содержание Helix VE 10 Series
Страница 2: ......
Страница 3: ...Fig 1...
Страница 4: ...Fig 2...
Страница 5: ...Fig 3 Fig 6 Fig 7...
Страница 7: ...Fig 8 Fig A1 1 1...
Страница 8: ...2 4 3 Fig 2D Fig 3D 4 3 2 Fig 4D 3 4 2...
Страница 130: ...130 WILO SE 03 2019 1 1 1 2 2 1 2 2 2 3 2 4 2 5...
Страница 131: ...131 HELIX VE 22 36 52 2 6 2 7 2 8 4 3 4 4 1...
Страница 135: ...135 HELIX VE 22 36 52 7 2 2 10 5 2 7 8 9 a b 10 A1 A2 A3 A4 1 _ 2 3 4 6 2 Helix Helix Helix 40 Helix 8 7 7 1...
Страница 136: ...136 WILO SE 03 2019 IP55 7 3 80 7 4 5 3 11 15 18 5 22 M32 M40 5 5 7 5 M25 0 55 0 75 1 1 1 5 2 2 3 4 M25...
Страница 142: ...142 WILO SE 03 2019 100 100 4 20 0 0 2 2 4 4 20 10 0 2 0 1 100 100 0 20 0 0 20 10 2 10 0 10 S1 S2...
Страница 147: ...147 HELIX VE 22 36 52 Fig A1 1 OFF OPERATION 1 OFF OPERATION PID 1 OFF OPERATION Information Service...
Страница 149: ...149 HELIX VE 22 36 52 Fig A2 EASY EXPERT EXPERT Fig A4 Information EASY Fig A3...
Страница 153: ...153 HELIX VE 22 36 52 Fig A5 Information SSM SBM Ext Off INFORMATION 4000...
Страница 154: ...154 WILO SE 03 2019 9 15 000 7 1 7 2 6 10 2 ON 7 0 0 0 2 OFF A1 1...
Страница 155: ...155 HELIX VE 22 36 52 Wilo 10 O cy c ye 20 30 Wilo...
Страница 156: ...156 WILO SE 03 2019 9 2 SBM 5 7 6 0 3 1 2 3 SSM 1 6 6 24 SBM 24 SBM SSM 1 2 3 4 5 6 24...
Страница 158: ...158 WILO SE 03 2019 10 2 6 0 0 0 24 1 6 300...
Страница 159: ...159 HELIX VE 22 36 52 11 Wilo www wilo com 12 www wilo recycling com...
Страница 196: ......