67
10.1 Faults table
All incidents mentioned hereafter will have the following effect:
•
Deactivation of the SBM relay (when parameterised in “available transfer” mode).
•
Activation of the SSM relay “failure transfer” when the max. quantity of one malfunction type is reached within a 24hour
period.
• Lighting of a red LED.
Error
code
Ramp time
before
signalling of
error
Time
before the
error
is taken into
account after
signalling
Waiting time
before
automatic
reactivation
Max.
error in
24 h
Faults
Possible causes
Remedies
Waiting
time
before
reset
E001
60 s
0 s
60 s
6
The pump is overloaded,
malfunctioning
Density and/or viscosity of the pumped
fluid too high
300 s
The pump is obstructed by
foreign bodies
Dismantle the pump, replace the
malfunctioning components or clean it
E004
(E032)
~5s
(0.55 to
7.5 kW)
300
s
(0.55 to 7.5 kW)
0
s if error
deleted
6
The power supply to the
converter is in undervoltage
Check the voltage at the converter
terminals
:
•
malfunction if power supply > 480 V
(0.55 to 7.5 kW)
•
malfunction if power supply > 506 V
(11 to 22 kW)
(0.55 to
7.5 kW)
0 s
(11 to 22 kW)
0 s
(11 to 22 kW)
300
s
(11 to
22 kW)
300 s
E005
(E033)
~5s
300
s
0 s if error
deleted
6
The power supply to the
converter is at overvoltage
Check the voltage at the converter
terminals
:
•
malfunction if power supply > 506 V
0 s
E006
~5s
300
s
0 s if error
deleted
6
A power supply phase is missing Check the power supply
0 s
E007
0 s
0 s
0 s if error
deleted
Un
limited
The converter operates as a
generator. Warning, no pump
deactivation
The pump has switched direction, check
the impermeability of the valve
0 s
E010
~5s
0 s
Unlimited
1
The pump is blocked
Dismantle pump, clean it and replace the
faulty parts. Possible mechanical motor
malfunction (roller bearings)
60 s
E011
15s
0 s
60 s
6
The pump is deactivated or is
running dry
Reprime by filling the pump (See §
9.3).
Check the impermeability of the foot valve
300 s
E020
~5s
0 s
300 s
6
The motor is heating up
Clean the cooling ribs at the back and
under the converter, as well as the fan cap
300 s
Room temperature above
product characteristics
Improve the ventilation of the premises
E023
0 s
0 s
60 s
6
The motor is short-circuited
Remove the motor-converter from the
pump and check it or replace it
60 s
E025
0 s
0 s
Unlimited
1
A phase of the motor is missing
Check the connection between the motor
and the converter
60 s
E026
~5s
0 s
300 s
6
The motor’s temperature
sensor is faulty or has a bad
connection
Remove the motor-converter from the
pump and check it or replace it
300 s
E030
E031
~5s
0 s
(0.55 to 7.5 kW)
0 s if error
deleted
(11 to 22 kW)
300 s
6
The converter is heating up
Clean the cooling ribs at the back and
under the converter, as well as the fan cap
300 s
Room temperature above
product characteristics
Improve the ventilation of the premises
E042
~5s
0 s
Unlimited
1
The sensor cable (IN1) is cut
Check for the correct power supply and
wiring to the sensor
60 s
E050
60 s
0 s
0 s if error
deleted
Un
limited
The BMS communication is
faulty
Check the connection
300 s
E077
0 s
0 s
Unlimited
1
24 V power supply voltage of
sensors faulty
Check the sensors and their connections
60 s
E---
0 s
0 s
Unlimited
1
Converter internal malfunction Call customer service
60 s
Installation and operating instructions – HELIXVE 223652
English
Содержание Helix VE 10 Series
Страница 2: ......
Страница 3: ...Fig 1...
Страница 4: ...Fig 2...
Страница 5: ...Fig 3 Fig 6 Fig 7...
Страница 7: ...Fig 8 Fig A1 1 1...
Страница 8: ...2 4 3 Fig 2D Fig 3D 4 3 2 Fig 4D 3 4 2...
Страница 130: ...130 WILO SE 03 2019 1 1 1 2 2 1 2 2 2 3 2 4 2 5...
Страница 131: ...131 HELIX VE 22 36 52 2 6 2 7 2 8 4 3 4 4 1...
Страница 135: ...135 HELIX VE 22 36 52 7 2 2 10 5 2 7 8 9 a b 10 A1 A2 A3 A4 1 _ 2 3 4 6 2 Helix Helix Helix 40 Helix 8 7 7 1...
Страница 136: ...136 WILO SE 03 2019 IP55 7 3 80 7 4 5 3 11 15 18 5 22 M32 M40 5 5 7 5 M25 0 55 0 75 1 1 1 5 2 2 3 4 M25...
Страница 142: ...142 WILO SE 03 2019 100 100 4 20 0 0 2 2 4 4 20 10 0 2 0 1 100 100 0 20 0 0 20 10 2 10 0 10 S1 S2...
Страница 147: ...147 HELIX VE 22 36 52 Fig A1 1 OFF OPERATION 1 OFF OPERATION PID 1 OFF OPERATION Information Service...
Страница 149: ...149 HELIX VE 22 36 52 Fig A2 EASY EXPERT EXPERT Fig A4 Information EASY Fig A3...
Страница 153: ...153 HELIX VE 22 36 52 Fig A5 Information SSM SBM Ext Off INFORMATION 4000...
Страница 154: ...154 WILO SE 03 2019 9 15 000 7 1 7 2 6 10 2 ON 7 0 0 0 2 OFF A1 1...
Страница 155: ...155 HELIX VE 22 36 52 Wilo 10 O cy c ye 20 30 Wilo...
Страница 156: ...156 WILO SE 03 2019 9 2 SBM 5 7 6 0 3 1 2 3 SSM 1 6 6 24 SBM 24 SBM SSM 1 2 3 4 5 6 24...
Страница 158: ...158 WILO SE 03 2019 10 2 6 0 0 0 24 1 6 300...
Страница 159: ...159 HELIX VE 22 36 52 11 Wilo www wilo com 12 www wilo recycling com...
Страница 196: ......