User Manual 5.32 (2018-05) 3
Subject to change
Series EK92
EK90 smoke control dampers
Description, properties, sizes
Fire classification
EI 90 (v
edw
- h
odw
- i
↔
o) S1500 C
mod
HOT400/30 MA multi
•
EI90
Fire resistance period of 90 minutes
Installation:
v
e d
in and on horizontal smoke extraction ducts.
h
o d
in and on vertical smoke extraction ducts.
v
e w
in rigid walls and in flexible walls.
h
o w
in rigid ceilings.
i ↔ o Fire exposure has been verified on both sides.
•
S1500
For smoke extraction systems with operating pressures
between
1500 Pa negative pressure and 500 Pa overpres
-
sure (pressure class 3).
Smokeproof at up to 1500 Pa differ
-
ential pressure.
•
C
mod
For systems designed only for smoke extraction and also for
combined ventilation systems that was as heating, ventila
-
tion and air conditioning systems.Intermediate damper blade
positions for volume flow adjustment are permitted (modula-
tion mode).
The service life is verified by 20,000 weight-loaded cycles.
•
HOT
The smoke control dampers close and open again at least
after 30 minutes of fire exposure at 400°C.
•
MA
Closed smoke control dampers can be opened after 25 min
-
utes of full exposure to fire (> 800°C).
•
multi
The smoke control dampers may be used between fire com-
partments (multi) and in individual areas (single).
Maintenance-free
EK90 smoke control dampers EN 12101-8 – Series EK92 –
With casing and damper blades made from abrasion-proof, safe,
corrosion-resistant calcium silicate that is suitable for higher
temperatures. The edge protection profiles are made from gal
-
vanized steel and include connection holes.
Opening and closing is carried out by means of stainless steel
shafts using electric motor drives for 24 V AC/DC or 230 V AC
even when the fan is running and at inflow velocities of up to
20 m/s.
Special seals without any additional stops allow for large free
cross-sections and thus extremely low pressure drops and
sound power levels.
Widths B
:
200 mm to 1500 mm
Heights H:
:
200 mm to 800 mm
Lengths L
:
350 mm to 850 mm
All dimensions are available in 5-mm
increments!
Installation
with horizontal or vertical damper
blade:
•
in rigid walls and ceilings,
≥
100 mm thick and
≥ 450 kg/m³ bulk density.Wet installation with
mortar or a dry installation with mineral wool
≥ 100
kg/m³ are possible.
•
in metal stud walls,
≥
95 mm thick, with or with-
out mineral wool ≤ 100 kg/m³ inside.
•
on and between horizontal or vertical smoke
extraction ducts.
Can be connected:
•
in single or double-sided arrangement on
smoke extraction ducts with fire resistance
period,
•
in single-sided arrangement on smoke extrac
-
tion ducts without fire resistance period,
•
in single or double-sided arrangement on pro
-
tective grille
⇒
see also page 34
Declaration of performance
DoP no. CPR/EK90/003
German approval
Z 56.4212 – 1007
Environmental Product Declaration according to ISO 14025 and
EN 15804 EPD-WIL-20160047-ICC1-DE
Casing leak tightness class C according to EN 1751