Wildeboer EK90 Скачать руководство пользователя страница 34

User Manual 5.32 (2018-05) 34

Subject to change 

Series EK92

Available in 

5 mm increments

:

 

Clear widths 

B = 200 mm to 1500 mm

 

Clear heights 

H = 200 mm to 800 mm

• 

Lengths

:

including

and

• 

lengths

 Special design of electrical 

connection

The  length  L2  comprises  the  thickness 

of  the  wall  W  or  ceiling  D  and  the  cas

-

ing  excess  length  Z. 

L2 = W (D) + Z 

⇒ 

see pages 4, 18, 19, 20 and 21

Generally, shear protection brackets A 

with Z = 100 mm and strips for shear 

protection should be mounted on the 

casing  of  the  smoke  control  dampers 

and all smoke extraction ducts should 

be connected at the same time. 

 

⇒ 

For shorter "Z" dimensions, see page references 

above!

EK90 smoke control dampers

Order data

Size:

• 

B [mm]  x  H [mm]  x  L [mm]

  • 

Standard design

  

    L = 500 mm if H 

≤ 

450 mm

  

 

    with L1 = 330 mm and L2 = 170 mm.

    L = 550 mm if H >

 

450 mm

  

 

    with L1 = 380 mm and L2 = 170 mm.
  

If smaller or longer lengths L are ordered,  

    then L1 = 330 mm or 380 mm is supplied  

    and L2 modified accordingly. 

  • 

Option:

 Special design

 

EA

 

   

Electrical connection

  

  L = 550 mm for all heights

  

  H = 200 mm to 800 mm and with 
  L1 = 380 mm and L2 = 170 mm.

    If smaller or longer lengths L are ordered,  

    then L1 = 380 mm is supplied and L2  

    modified accordingly. 

Option: 

Special length L1 [mm]

   

L1 = 380, 400, 425, 450, 475, 500, 525 mm;  

L= L1 + L2 should be ordered!

⇒ 

see page 4

Option:

 Versions with reduced frame 

height for

 

 

• 

Motor drive on the left

 NL 

• 

Motor drive on the right

 NR 

⇒ 

see page 29

Motor drive

 

 

•  24

 V AC/DC

 

with AMP connector

 

M1

 

•  230

 V AC 

M2

⇒ 

see page 30

Options:

 

• 

Terminal strip 

for motor drive

 

KL 

 

⇒ 

see page 30

• 

Additional casing 

for control units

 Z 

 

⇒ 

see page 32

With 

shear protection brackets 

 for non-drive-side attachment

 

A

 

• 

for drive-side attachment 

B

 

in rigid walls and ceilings;  

 

otherwise not required.  

 

Shear  protection  brackets  A  are  included  in 

the delivery as standard!

EK92 - 

  - - - - --

Protective grille

 made from 1 mm galvanized sheet steel 

with 20 mm mesh size and approx. 70% free cross-section. 

 Available dimensions: B x H   

⇒ 

see pages 23 and 27

Part of scope of delivery:

 2 x support bearings for gap width s = 25 mm

• 

Stopper seal with adhesive 

• 

1 set of shear protection brackets A or B, if specifically ordered.

L = L1 + L2

≤ 

450

H > 450

350 to 850

400 to 850

L1

≤ 

450

H > 450

330 to 480

380 to 530

L2

≤ 

450

H > 450

20 to 370

20 to 320

All dimensions in mm

Lengths for double-sided mounting of protec-

tive grilles

Without excess lengths P1 and P2   

⇒ 

see page 4

for heights H  Length L  Length L1  Length L2

up to 400 mm:  450 mm 

330 mm 

120 mm

up to 500 mm:  550 mm 

380 mm 

170 mm

up to 550 mm:  600 mm 

400 mm 

200 mm

up to 600 mm:  650 mm 

425 mm 

225 mm

up to 650 mm:  700 mm 

450 mm 

250 mm

up to 700 mm:  750 mm 

475 mm 

275 mm

up to 750 mm:  800 mm 

500 mm 

300 mm

up to 800 mm:  850 mm 

525 mm 

325 mm

Содержание EK90

Страница 1: ...n of this document shall prevail Maintenance free EK90 smoke control dampers meet all requirements in accordance with European standards and are universal for all applications Further uses and extende...

Страница 2: ...l damper Opened smoke control damper Ventilator for smoke extraction and also for ventilation Smoke extraction duct with fire resistance period Smoke extraction duct without fire resistance period Smo...

Страница 3: ...g and damper blades made from abrasion proof safe corrosion resistant calcium silicate that is suitable for higher temperatures The edge protection profiles are made from gal vanized steel and include...

Страница 4: ...action ducts for heights H Length L Length L1 Length L2 up to 450 mm 350 mm 330 mm 20 mm larger than 450 mm 400 mm 380 mm 20 mm Standard widths B mm 200 225 250 275 300 325 350 375 400 450 500 550 600...

Страница 5: ...698 0 689 0 682 0 676 250 0 768 0 732 0 704 0 682 0 664 0 649 0 637 0 626 0 617 0 602 0 590 0 581 0 573 0 566 0 561 275 0 669 0 636 0 610 0 590 0 574 0 560 0 549 0 539 0 531 0 517 0 506 0 497 0 490 0...

Страница 6: ...t B 500 mm with H 500 mm lies in the field A Max 20 m s There is no restriction here see also table on page 7 v A Max m s 6 5 5 5 3 2 1 20 30 70 100 7 200 250 300 350 400 500 600 700 800 1000 1200 150...

Страница 7: ...0 2000 4000 8000 vA 5 m s 16 8 2 4 8 12 15 19 vA 10 m s 10 4 1 4 6 9 12 16 vA 15 m s 5 2 0 4 6 7 11 15 vA 20 m s 2 1 2 5 6 7 11 14 Examples 1 2 3 Width B x height H Inflow velocity vA 10 15 20 m s Vol...

Страница 8: ...4 34 34 33 33 33 33 33 33 33 33 33 33 33 33 400 m h 1440 1620 1800 1980 2160 2340 2520 2700 2880 3240 3600 3960 4320 4680 5040 Pa 6 6 6 5 5 5 5 5 5 5 5 4 4 4 4 dB A 34 33 33 33 33 33 33 33 33 33 32 32...

Страница 9: ...32 32 32 400 m h 5400 5760 6120 6480 6840 7200 7560 7920 8280 8640 9000 9360 10080 10800 Pa 4 4 4 4 4 4 4 4 4 4 4 4 4 4 dB A 32 32 32 32 32 32 32 32 32 32 32 32 32 32 450 m h 6075 6480 6885 7290 7695...

Страница 10: ...50 50 400 m h 2880 3240 3600 3960 4320 4680 5040 5400 5760 6480 7200 7920 8640 9360 10080 Pa 26 24 23 22 21 21 20 20 19 19 18 18 17 17 17 dB A 51 51 51 51 51 51 51 50 50 50 50 50 50 50 50 450 m h 3240...

Страница 11: ...50 50 50 50 50 50 50 50 50 50 400 m h 10800 11520 12240 12960 13680 14400 15120 15840 16560 17280 18000 18720 20160 21600 Pa 17 16 16 16 16 16 16 16 16 16 16 16 15 15 dB A 50 50 50 50 50 50 50 50 50...

Страница 12: ...44 43 42 42 41 dB A 63 62 62 62 62 62 62 62 62 61 61 61 61 61 61 400 m h 4320 4860 5400 5940 6480 7020 7560 8100 8640 9720 10800 11880 12960 14040 15120 Pa 58 54 51 49 48 46 45 44 43 42 41 40 39 38 3...

Страница 13: ...2 62 62 350 m h 14175 15120 16065 17010 17955 18900 19845 20790 21735 22680 23625 24570 26460 28350 Pa 45 44 44 44 43 43 43 43 43 42 42 42 42 42 dB A 61 61 61 61 61 61 61 61 61 61 61 61 61 61 375 m h...

Страница 14: ...17640 Pa 118 112 107 103 99 97 94 93 91 88 86 84 83 82 81 dB A 71 71 70 70 70 70 70 70 70 70 70 70 69 69 69 375 m h 5400 6075 6750 7425 8100 8775 9450 10125 10800 12150 13500 14850 16200 17550 18900...

Страница 15: ...520 21600 22680 23760 24840 25920 27000 28080 30240 32400 Pa 100 99 98 97 97 96 96 95 95 95 94 94 94 93 dB A 70 70 70 70 70 70 70 70 70 70 70 70 70 70 325 m h 17550 18720 19890 21060 22230 23400 24570...

Страница 16: ...0 788 0 825 0 861 0 898 0 934 1 007 1 080 H B 200 225 250 275 300 325 350 375 400 450 500 550 600 650 700 200 0 023 0 027 0 030 0 033 0 036 0 040 0 043 0 046 0 049 0 056 0 062 0 069 0 075 0 082 0 088...

Страница 17: ...3 76 78 80 83 85 88 90 93 98 102 225 67 70 72 75 77 80 82 85 87 90 92 95 100 105 250 69 72 74 77 79 82 84 87 89 92 94 97 102 107 275 71 73 76 78 81 84 86 89 91 94 96 99 104 109 300 72 75 78 80 83 85 8...

Страница 18: ...installation s 25 mm Gap for mineral wool filling s 10 to 25 mm Calcium silicate support bearings with the dimensions 100 mm x 100 mm x 25 mm for gaps s 25 mm are included in delivery Support bearings...

Страница 19: ...ection brackets B are fitted onto the oper ation side front of the smoke control damper and are attached using M8 threaded rods and nuts that pass through the wall or ceiling Dowel attachment see page...

Страница 20: ...ng DA 125 mm up to 180 mm Shear protection brackets A can be used laterally and shear protection brackets B above and below Spacing DA 22 mm Shear protection brackets A or B can be used laterally Spac...

Страница 21: ...vertical sides For the length L of the smoke control dampers excess lengths of Z 70 mm are required to fit the strips or excess lengths of Z 100 mm if smoke extraction ducts with fire resistance peri...

Страница 22: ...in the same way EK90 smoke control dampers in metal stud walls with cladding on both sides directly adjoining rigid walls and ceilings Detail A Shear protection strips see page 21 Detail B The 52 mm s...

Страница 23: ...smoke control dampers see page 28 Example Left hand side smoke extraction duct made from sheet steel right hand side smoke extraction duct made from wall boards with fire resistance period The connec...

Страница 24: ...specifications The screw sizes specified in the following drawings relate to smoke extraction ducts with a thickness of 35 mm The screw lengths should be adapted in the case of greater thicknesses Ins...

Страница 25: ...installation Extensions must be produced from duct specific materials in the cross section 50 mm x 70 mm glued to the smoke extraction duct and screwed on using chipboard screws with a diameter of 5 x...

Страница 26: ...smoke extraction ducts with clear widths Hsmoke control damper 130 mm Installation opening Completed installation Section A A Longitudinal view Detail from section A A Damper blade excess length 2 se...

Страница 27: ...om of movement of the damper blade should be taken into account when mounting the protective grilles see damper blade excess length on page 4 Extensions in the form of smoke extraction ducts made from...

Страница 28: ...sion of an EK90 smoke control damper together with connected smoke extraction ducts Weights of EK90 smoke control dampers see page 17 Example EK90 smoke control dampers between vertical smoke extracti...

Страница 29: ...1 H Installation opening 22 Z Mineral wool 100 kg m or Mortar Calcium silicate strips for shear protection Chipboard screws 4 x 60 at spacing of 200 mm Installation direction NL NR 22 W Installation...

Страница 30: ...AC DC Electrical connection Motor drives M2 230 V AC Motor drive for standard design with heights H 200 to 450 mm Motor drive for standard design with heights H 450 up to 800 mm and for special design...

Страница 31: ...ng the connection cables this should be factored in with large cross sections shorter lengths or a higher electrical operating volt age accordingly The same applies to connection cables for operating...

Страница 32: ...through the walls of the extra casings can be produced on site The clear dimension of the additional casing depends on the type of EK90 smoke control damper Design Heights H mm Clear dimen sion mm Sta...

Страница 33: ...eboer de In general actuating closing and opening the smoke control dampers is sufficient in testing the function This can be performed by means of remote actuation EK90 smoke control dampers do not g...

Страница 34: ...should be ordered see page 4 Option Versions with reduced frame height for Motor drive on the left NL Motor drive on the right NR see page 29 Motor drive 24 V AC DC with AMP connectorM1 230 V AC M2 se...

Страница 35: ...With special seals to open and close the smoke con trol dampers during fire exposure For installation in rigid walls and ceilings with mortar or mineral wool in flexible walls and onto or between smo...

Страница 36: ...wildeboer eu WEENER EMS Ulm office Telephone 49 0 7392 9692 0 Fax 49 0 4951 950 27299 E mail info ulm wildeboer de ULM Leipzig office Telephone 49 0 34444 310 0 Fax 49 0 4951 950 27298 E mail info le...

Отзывы: