65
9 Maintenance and fault rectification
WIKA Operating Instructions - Differential pressure transmitter DPT-10
Error code
Cause
Rectification
E013
no measured value
available
6)
– Exchange the instrument or send it
in for repair
E017
Adjustment span too
small
– repeat with modified values
E036
no operable sensor
software
– Carry out a software update or send
instrument for repair
E041
Hardware error
– Exchange the instrument or send it
in for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "
Set up
" may have to be carried out again.
9.3 Instrument repair
You can find information for a return shipment under "
Service
" on our
local website.
If a repair is necessary, please proceed as follows:
•
Complete one form for each instrument
•
If necessary, state a contamination
•
Clean the instrument and pack it damage-proof
•
Attach the completed form and possibly also a safety data sheet to
the instrument
Error messages via the
display and adjustment
module
Reaction after fault recti-
fication
6)
Fault message can also appear if the pressure is higher than the nominal
range.