11 Supplement
WIKA Operating Instructions - Differential pressure transmitter DPT-10
Chemical seal versions
100 mbar measuring cell
Ʋ Turn down 1 : 1 to 4 : 1
±0.075 % of the set span + influence of the chemical
seal
Ʋ Turn down > 4 : 1
±(0.012 x TD + 0.027) % of the set span + influence of
the chemical seal
Measuring cells ≥ 500 mbar
Ʋ Turn down 1 : 1 to 15 : 1
±0.075 % of the set span + influence of the chemical
seal
Ʋ Turn down > 15 : 1
±(0.0015 % x TD + 0.053 %) of the set span + influence
of the chemical seal
Influence of the medium or ambient temperature
Thermal change zero signal and output span
Applies to instruments in basic version with
digital
signal output (HART, Profibus PA, Foundation
Fieldbus) as well as to instruments with
analogue
current output 4 … 20 mA. Specifications refer
to the set span. Turn down (TD) = nominal measuring range/set span.
Temperature range
Measuring range
-10 … +60 °C (+14 … +140 °F)
10 mbar, 30 mbar
±(0.30 x TD + 0.06) %
100 mbar
±(0.18 x TD + 0.02) %
500 mbar, 3 bar
±(0.08 x TD + 0.05) %
16 bar
±(0.1 x TD + 0.1) %
40 bar
±(0.08 x TD + 0.05) %
-40 … +10 °C (-40 … +50 °F)
+60 … +85 °C (+140 … +185 °F)
10 mbar, 30 mbar
±(0.45 x TD + 0.1) %
100 mbar
±(0.3 x TD + 0.15) %
500 mbar, 3 bar
±(0.12 x TD + 0.1) %
16 bar
±(0.15 x TD + 0.2) %
40 bar
±(0.37 x TD + 0.1) %
Thermal change, current output
Applies also to instruments with
analogue
4 … 20 mA current output and refers to the set span.
0,3 %
-0,15 %
-40°C
-20°C
20°C
40°C
60°C
80°C
0,15 %
-0,3 %
Fig. 51: Thermal change, current output
Influence of the system pressure on the zero point and span
316L, Alloy C276 (2.4819), Alloy 400 (2.4360) diaphragm