Installation, operating and maintenance manual
UNIGAS 300
DDG6004MHGB/08-2017/Rev.A2 Software version from M 1.3.40 and D 2.3.37
36
Processed counter readings; consumption values recorded for input 1
Name
Unit
Menu item
OBIS code
Description
Qc1_5
m
3
/h
3-1
7-1:43.1.1
Flow at measuring conditions based upon 5 minutes
interval, total value
Qc1_nx5
m
3
/h
3-1
7-1:43.1.2
Flow at measuring conditions, based upon the moving
average of n x 5 minutes interval, total value
Qc1_inst
m
3
/h
3-1
7-1:43.1.0
Instantaneous flow rate, corrected and unconverted total
value
Vc1_60
m
3
3-2
7-1:43.1.71
Consumption in actual hour, total volume at measuring
conditions
Qb1_5
m
3
/h
3-2
7-1:43.2.1
Flow at base conditions, undisturbed value based upon 5
minutes interval
Qb1_nx5
m
3
/h
3-2
7-1:43.2.2
Flow at base conditions, undisturbed value based upon the
moving average of n x 5 minutes interval
Qb1_inst
m
3
/h
3-2
7-1:43.2.0
Instantaneous flow, undisturbed value at measuring
conditions
Vb1_60
m
3
3-2
7-1:43.2.71
Consumption in actual hour, undisturbed volume
Miscellaneous functions, protection level 2b
Name
Unit
OBIS code
Description
Flow rate
measurement n
-
C.93.1
Time base for determining flow rate Q based on the moving
average of n units of 5 min
Objects resulting from the conversion /measured values
Name
Unit
Menu
item
OBIS code
Description
Cf
-
1-1
7-1:51.0.0
Current correction value of the gas meter measuring error
C
-
1-1
7-1:52.2.0
Calculated conversion factor
Z
-
1-1
7-1:53.0.0
Gas compressibility under operating conditions
Z/Zb
-
1-1
7-1:53.2.0
Gas compressibility factor
p
mbar
1-1
7-1:42.0.0
Pressure
t
°C
1-1
7-1:41.0.0
Temperature