background image

8

Start-up Procedure—Heat Pump

1.

Check that the cooling mode for the heat pump is working 
properly according to the procedure listed in the “Start-up 
Procedure—Cooling Cycle” section.

The reversing valve is energized when the thermostat is 
placed in the cooling position. 

A clicking sound should be noticeable from the reversing 
valve. 

By lowering the temperature setting to call for cooling, the 
contactor is energized. 

The compressor, blower and fan should then be running. 

2.

After the cooling mode is checked out, turn the thermostat 
system switch to “OFF.”

3.

Turn the thermostat switch to “HEAT” and the fan switch to 
“AUTO.”

4.

Slowly raise the heating temperature setting. When the 
heating 1

st

 stage makes contact, stop raising the temperature 

setting. The compressor, blower and fan should now be 
running with the reversing valve in the deenergized (heating) 
position. 

5.

After giving the unit time to settle out, check that the unit is 
supplying heated air.

6.

If the outdoor ambient is above 80°F (26.7ºC), the unit may 
trip on its high pressure cutout when on heating. The 
compressor should stop. 

7.

The heating cycle must be thoroughly checked, so postpone 
the test to another day when conditions are more suitable.

IMPORTANT:

 Be sure to test the unit.

8.

If the outdoor ambient is low and the unit operates properly 
on the heating cycle, you may check the pressure cutout 
operation by blocking off the indoor return air until the unit 
trips.

9.

If the unit operates properly in the heating cycle, raise the 
temperature setting until the heating 2

nd

 stage makes contact. 

Supplemental resistance heat, if installed, should now turn 
on. Check that the supplemental resistant heat operates 
properly.

NOTES:

 

WGPH4549-60 has 2 stages of compressor heat. During 
the resistance heat test, increase the temperature setting 
until the 3

rd

-stage heat is energized.

If outdoor thermostats are installed, the outdoor ambient 
temperature must be below the set point of these 
thermostats for the heaters to operate. It may be 
necessary to jumper these thermostats to check heater 
operation if outdoor ambient temperature is mild.

10.

For thermostats with an emergency heat switch, raise the 
temperature setting until the heating 2

nd

 stage makes contact. 

NOTE: 

The emergency heat switch is located at the bottom 

of the thermostat. Move the switch to emergency heat. The 
heat pump will stop, the blower will continue to run, all 
heaters will come on, and the thermostat emergency heat 
light will turn on.

11.

If the unit is being checked in the wintertime when the 
outdoor coil is cold enough to activate the defrost control, 
observe at least one defrost cycle to make sure the unit 
defrosts completely.

Final System Checks

1.

Check that all supply and return air grilles are adjusted and 
the air distribution system is balanced for the best 
compromise between heating and cooling.

2.

Check for air leaks in the ductwork. See “Airflow 
Measurement and Adjustment” and “Checking Charge.”

3.

Check that the unit is free of “rattles,” and the tubing in the 
unit is free from excessive vibration. 

4.

Check that the tubes and lines are not rubbing against each 
other or against the sheet metal surfaces or edges. If contact 
is found, correct the problem.

5.

Set the thermostat at the appropriate setting for cooling and 
heating or automatic changeover for normal use.

6.

Check that the owner is instructed on the unit operation, filter, 
servicing, correct thermostat operation, etc.

7.

The previous sections are recommended to serve as an 
indication that the unit will operate normally.

Explanation and Guidance—Heat Pump

When the heat pump is in the cooling cycle, the heat pump 
operates exactly as an air conditioning unit.

The heat pump operates in the heating cycle by redirecting 
refrigerant flow through the refrigerant circuit external to the 
compressor. This is accomplished through the reversing valve. 
Hot discharge vapor from the compressor is directed to the 
indoor coil (evaporator on the cooling cycle) where the heat is 
removed, and the vapor condenses to a liquid. It then goes 
through the expansion device to the outdoor coil (condenser on 
the cooling cycle) where the liquid is evaporated, and the vapor 
goes to the compressor.

When the solenoid valve coil is operated either from heating to 
cooling or cooling to heating, the piston in the reversing valve to 
the low pressure (high pressure) reverses position in the reversing 
valve.

The following illustrations show a schematic of a heat pump on 
the cooling cycle and the heating cycle. In addition to a reversing 
valve, a heat pump is equipped with an expansion device and 
check valve for the indoor coil, and similar equipment for the 
outdoor coil. It is also provided with a defrost control system.

The expansion devices are flowrator distributors and perform the 
same function on the heating cycle as on the cooling cycle. The 
flowrator distributors also act as check valves to allow for the 
reverse of refrigerant flow.

When the heat pump is on the heating cycle, the outdoor coil is 
functioning as an evaporator. The temperature of the refrigerant 
in the outdoor coil must be below the temperature of the outdoor 
air in order to extract heat from the air. Thus, the greater the 
difference in the outdoor temperature and the outdoor coil 
temperature, the greater the heating capacity of the heat pump. 
This phenomenon is a characteristic of a heat pump. It is a good 
practice to provide supplementary heat for all heat pump 
installations in areas where the temperature drops below 45°F 
(7.2ºC). It is also a good practice to provide sufficient 
supplementary heat to handle the entire heating requirement 
should there be a component failure of the heat pump, such as a 
compressor, refrigerant leak, etc.

Since the temperature of the refrigerant in the outdoor coil on the 
heating cycle is generally below the freezing point, frost forms on 
the surfaces of the outdoor coil under certain weather conditions. 
Therefore, it is necessary to reverse the flow of the refrigerant to 
provide hot gas in the outdoor coil to melt the frost accumulation. 

Goodman 6

HIGH VOLTAGE!

WARNING

Disconnect ALL power before servicing.

Multiple power sources may be present.

Failure to do so may cause property damage, 
personal injury or death.

Содержание Gold WGPH45**AM

Страница 1: ...ectric Heat Installation and Adjustment 6 Make Electrical Connections 6 Complete Installation 7 SEQUENCE OF OPERATION 7 Start up Procedure Cooling Cycle 7 Start up Procedure Heat Pump 8 Final System Checks 8 Explanation and Guidance Heat Pump 8 Defrost Cycle 9 System Troubleshooting 10 Circulating Air Blower 11 Blower Performance Data 12 CHARGE VERIFICATION 14 SYSTEM MAINTENANCE 16 TROUBLESHOOTING...

Страница 2: ...e unit be placed so that the condenser air discharge does not blow toward windows less than 25 ft 7 6 m away Heat pumps require special location consideration in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to allow fr...

Страница 3: ...g and general roofing material are furnished by the contractor Curbing must be installed in compliance with the National Roofing Contractors Association Manual Construct ductwork using current industry guidelines The ductwork must be placed into the roof curb before mounting the package unit Minimum Clearances The unit is designed to be located outside the building with an unobstructed condenser a...

Страница 4: ... outdoor use Use copper conductors only All field wiring must be done in accordance with National Electrical Code requirements applicable requirements of UL or local codes where applicable Electrical wiring disconnect means and over current protection are to be supplied by the installer Refer to the rating plate for the maximum over current protection minimum service ampacity and operating voltage...

Страница 5: ... and must be supplied and installed in the return duct system by the installer A field installed filter grille is recommended for easy and convenient access to the filters for periodic inspection and cleaning Filters must have adequate face area for the rated quantity of the unit See the Air Delivery Table for the recommended filter size Air Delivery Table Goodman 109 To prevent property damage th...

Страница 6: ... of larger size than indicated could result in extensive damage to the equipment The manufacturer bears no responsibility for damage caused to equipment as result of the use of larger than is recommended size protective devices All units have undergone a run test prior to packaging for shipment This equipment has been started at minimum rated voltage and checked for satisfactory operation Do not a...

Страница 7: ...2 Dispose of recycle all packaging materials 3 Check the heat pump or condensing unit in its final location SEQUENCE OF OPERATION Start upProcedure CoolingCycle 1 Disconnect power 2 Turn the thermostat switch to Cool and the fan switch to Auto 3 Set the temperature setting to the highest setting 4 Verify that all of the registers are set to the normal open position 5 Turn on the electrical supply ...

Страница 8: ...s free from excessive vibration 4 Check that the tubes and lines are not rubbing against each other or against the sheet metal surfaces or edges If contact is found correct the problem 5 Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use 6 Check that the owner is instructed on the unit operation filter servicing correct thermostat operation...

Страница 9: ...d the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 60 F 16ºC the defrost cycle is terminated and the timing period is reset If the defrost cycle is not terminated due to the sensor temperature a 10 minute override interrupts the unit s defrost period Circuit Board Suggested Field Testing Troubleshooting 1 Run the unit in the heating ...

Страница 10: ...citor weak open or shorted Check for unit voltage at compressor Check and tighten all connections Wait at least 2 hours for overload to reset If still open replace the compressor At compressor terminals voltage must be within 10 of nameplate volts when unit is operating Check capacitor Replace if defective Low suction Cool compressor iced evaporator coil Low indoor airflow Increase speed of blower...

Страница 11: ... be changed according to the electric heat size The ECM motor provides many features not available on the traditional PSC motor These features include Improved Efficiency Constant CFM Soft Start and Stop Improved Humidity Control ECM Motor Speed Adjustment Each ECM blower motor has been preprogrammed for operation at 4 distinct airflow levels when operating in Cooling Heat Pump mode or Electric He...

Страница 12: ... 889 819 Watts 202 214 221 229 235 246 258 264 T4 T5 CFM 1 267 1 213 1 162 1 120 1 058 1 009 932 841 Watts 218 226 236 245 247 260 272 275 WPC4542AM T1 CFM 1 123 1 070 1 025 984 942 894 839 774 Watts 162 170 182 193 204 216 229 242 T2 T3 CFM 1 437 1 390 1 354 1 318 1 281 1 243 1 204 1 165 Watts 310 317 331 342 355 366 377 389 T4 T5 CFM 1 528 1 490 1 450 1 410 1 383 1 348 1 312 1 267 Watts 372 379 ...

Страница 13: ... 1 700 B Plus 1 870 B Plus 1 870 A Minus 1 620 A Minus 1 620 A Normal 1 800 A Normal 1 800 A Plus 1 980 A Plus 1 980 WGPH4560AM Cooling HP Speed Adjust Tap CFM Electric Heat Adjust Tap CFM D Minus 1 260 D Minus 1 260 D Normal 1 400 D Normal 1 400 D Plus 1 540 D Plus 1 540 C Minus 1 440 C Minus 1 440 C Normal 1 600 C Normal 1 600 C Plus 1 760 C Plus 1 760 B Minus 1 620 B Minus 1 620 B Normal 1 800 ...

Страница 14: ...n 800 CFM Output for DIP Switch Combinations 5 and 6 Cooling Heating Model Speed Tap Switch 5 Switch 6 Cooling HP CFM WGPH4543 A Off Off 1 800 B On Off 1 700 C Off On 1 400 F D On On 1 225 WGPH4549 A Off Off 1 800 B On Off 1 700 C Off On 1 400 D On On 1 225 F WGPH4560 A Off Off 2 000 F B On Off 1 800 C Off On 1 600 D On On 1 400 DIP Switch Settings for Single and 2 Stage Thermostats Model Switch 3...

Страница 15: ...ithin limits Charge the unit on low stage 1 Purge the gauge lines 2 Connect the service gauge manifold to the access fittings Run the system for at least 10 minutes to allow the pressure to stabilize 3 Temporarily install a thermometer on the liquid small line near the liquid line access fitting with adequate contact and insulate for best possible reading 4 Check subcooling and superheat The 2 sta...

Страница 16: ... The return air filter must always be clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high pressure cutout Outside Air Into Return Duct Do not introduce cold outside air into the return duct of a heat pump installation Do not allow air entering the indoor coil to drop below 65 F 18ºC Air below this temperature will cause low discharge p...

Страница 17: ...V 208 TR C BK 1 R COMP CM BR 4 1 PLF BK Y S BK R 5 6 2 3 C R R O C W2 W1 G a t o t s m r e h T T2 T1 BU NOTE 2 PR L1 BU GND C L2 PR BK 60 1 0 4 2 8 0 2 7 8 9 BU BR W R R BK BK R Y BU BU R R DFT RVC LPS L 3 1 2 DC DFT DFT Y C R W2 O W1 Y1 G COM 4 5 6 PLF LVDR R R O O W2 HPS C If Used N G RVC See NOTE 4 SA If Used See NOTE 3 R Y BK BK BK OR OR W HPS Y BU BU BU BU Y Y LPS YCON OT2OT1 OTC O W W2 E W1 ...

Страница 18: ...K R 5 6 2 3 C R R O C W2 W1 G Y1 a t o t s m r e h T T2 T1 BU NOTE 2 PR L1 BU GND C L2 PR BK 60 1 0 4 2 8 0 2 7 8 9 BU BR W R R BK BK R Y BU BU R R DFT RVC LPS L 3 1 2 DC DFT DFT Y C R W2 O W1 Y1 G COM 4 5 6 PLF LVDR R R O O W2 HPS C If Used N G RVC See NOTE 4 SA If Used See NOTE 3 R Y BK BK BK OR OR W HPS Y BU BU Y BU BU Y Y LPS SOL BU Y BU YCON S0L OT2OT1 OTC O W W2 E W1 R YCON C OMO W2 ED OU TD...

Страница 19: ...A S T1 R L1 C NOTE 4 H F RCCF CM T2 C L2 Box H RCCF F C Y BR PR 2 24V 208 TR C BK 1 PR COMP CM BR BR PR 4 1 PLF PR BK Y S BK R BK 5 6 2 3 C R LVJB R BU BR W G Y R C W2 W1 G Y a t o t s m r e h T T2 T1 R BU NOTE 3 PR BU L1 GND C L2 PR BK 60 1 0 4 2 8 0 2 7 8 9 BU BR R R BK BK R C L G N 1 2 3 BU BU R G G G R EM G See NOTE 2 1 L 3 1 2 R W2 W1 Y G C 4 5 6 PLF EM 1 C See NOTE 2 If Used Thermostat N G 2...

Страница 20: ...time phone number in your correspondence Accessories To order accessories contact your Whirlpool Home Cooling and Heating dealer WPIO 362 2010 All rights reserved Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Jacksonville Florida Warranty provided by manufacturer All other trademarks are owned by their respective companies 2 ...

Отзывы: